IOMM ACZ1
ACZ 010A through 039A
39
SET UNIT SPs (6)
Evaporator Refrig
Press Sensor
Offset= 00.0 psi
The pressure offsets on menus 8 and 9 and the temperature offsets on menus 10 and 11 correct the
controller's display of the parameters. The sensors used in these units have a high degree of
repeatability but may need correction (offset). An accurate pressure gauge or thermometer is used to
determine the correct temperature or pressure. A positive or negative offset value is then entered to
make the controller reading agree with the measured value.
SET UNIT SPs (7)
Condenser Refrig
Press Sensor
Offset= 00.0 psi
SET UNIT SPs (8)
Outside Ambient
Temperature Sensor
Offset= 00.0
o
F
SET UNIT SPs (9)
ENTER PASSWORD XXXX
Active Password
Level:None
Two four-digit passwords provide OPERATOR and MANAGER levels of access to changeable
parameters. The passwords are preprogrammed into the controller. The Operator Password is 0100.
Either password must be entered using the ENTER PASSWORD (12) screen before a protected
setting can be changed.
This screen can be accessed either through the SET OTHER menu or by simply pressing the ENTER
key while on one of the SET screens. The controller will automatically go from the screen with the
setting change to this screen. After the correct password has been entered, the controller will
automatically return to the original set screen.
Once a password has been entered, it remains valid for 15 minutes after the last key-press.
SET COMP SPs
SET COMP SPs (1)
Stop-Start =XXmin
Start-Start =XXmin
This menu sets the anti-recycle timers. Stop-Start is the time required before starting a compressor
after it has
stopped
. Start-Start is the time required before starting a compressor after the last time it
has
started
. It is recommended that these default values not be changed.