1-11
English
•
All wires must be firmly connected.
•
Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.
•
The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage.
•
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
•
Make sure no external pressure is applied to the terminal connectors and wires.
•
Make sure all the covers are properly fixed to avoid any gap.
•
Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching to
the indication on terminal block. (Refer to the wiring diagram attached on the unit).
Connect wires of the
same gauge to both side.
Do not connect wires of the
same gauge to one side.
Do not connect wires
of different gauges.
•
Use the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
•
Over tightening can damage the terminal screws.
•
Do not connect wire of different gauge to same terminal.
•
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
IMPORTANT:
* These values are for information only. They should be checked and selected to comply with local and/or
national codes and regulations. They are also subject to the type of installation and size of conductors.
Model
Indoor
5CEY40ER
5CEY50ER
Outdoor
5SLY40ER
5SLY50ER
Voltage range
220-240V/1Ph/50Hz +
!
Power supply cable size*
mm
2
6
6
Number of conductors
3
3
Interconnection cable size*
mm
2
1.5
1.5
Number of conductors
4
4
Recommended time delay fuse*
A
32
32
5CEY40ER - 5SLY40ER
5CEY50ER - 5SLY50ER
Power Supply
Cable
Outdoor Unit
Terminal Block
Indoor Unit
Terminal Block
L
N
3
!
!
2
1
3
2
1
!
Attach insulation sleeve
Round crimp-style terminal
Electric wire
The electrical power must be provided with
protection devices (circuit breaker or fuse)
with double pole separation system (phase +
neutral) with minimum contact gap of 3.0mm.
!
ELECTRICAL WIRING CONNECTION
Interconnection
Cable
1 IM-5CEYER-1009(0)-EN
2/11/10, 4:29 PM
11