INSTRUCTION MANUAL FOR: 

 

T15 AIR CONDITIONER

 

 

McLean Thermal 
11611 Business Park Blvd. N   Champlin, MN 55316 
Tel: 763-323-8200   Fax: 763-576-3200 

 
www.mcleanthermal.com

 

Содержание T15-0116-GXXX Series

Страница 1: ...INSTRUCTION MANUAL FOR T15 AIR CONDITIONER McLean Thermal 11611 Business Park Blvd N Champlin MN 55316 Tel 763 323 8200 Fax 763 576 3200 www mcleanthermal com...

Страница 2: ...n and packing material and request an inspection Then file a claim with the delivering carrier McLean Thermal cannot accept responsibility for freight damages however we will assist you in any way pos...

Страница 3: ...ill continue to operate and the compressor will restart after it has cooled to within the thermal overload cut in temperature setting INSTALLATION Step 1 Inspect air conditioner Verify functionality b...

Страница 4: ...ltage Hz Amps Phase Temp o F o C Lbs Kgs T15 0116 GXXX 115 60 3 6 1 800 131 55 27 12 3 T15 0116 GXXX 100 50 3 8 1 800 125 52 27 12 3 T15 0126 GXXX 230 60 1 5 1 900 131 55 27 12 3 T15 0126 GXXX 220 50...

Страница 5: ...0 Coil Condenser 15 1001 02 15 1001 02 Coil Condenser Coated 15 1001 01 15 1001 01 Coil Evaporator 15 1001 03 15 1001 03 Compressor 10 1016 82 10 1026 101 Filter Air Reusable 10 1000 91 10 1000 91 Fil...

Страница 6: ...10 1008 194 Rev 2 Page 5 T15 Wire Diagram T15 Schematic...

Страница 7: ...is hermetically sealed properly lubricated at the factory and should provide years of satisfactory operating service Should the refrigerant charge be lost recharging ports access fittings on the suct...

Страница 8: ...sis The inlet air filter is located behind the front cover To access filter pull ring protruding from slot in bottom of front cover The filter may now be cleaned or new filter installed Cleaning Instr...

Страница 9: ...O possible Defective thermostat Open motor winding Stuck fan motor Obstructed blades 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compre...

Страница 10: ...t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Under sized breaker fuse or not time del...

Страница 11: ...s will assume the balance of the warranty on the part returned for warranty consideration Please be advised According to the Federal Register no person maintaining servicing repairing or disposing of...