McDonnell & Miller 1575 Series Скачать руководство пользователя страница 1

Series 1575

Low Water Cut-Off/Pump Controller

For Steam Boilers and Other Level Control Applications

FEATURES

Probe Chamber:

• Cast Iron Body
• Sight Glass Tappings
• Gage Cock Tappings
• Stainless Steel Probes
• NEMA 4X Electrical Enclosure
• 250 psi Maximum Working Pressure

Probe Chamber

Electronic Control Unit

• Before using this product read and understand instructions.

• Save these instructions for future reference.

• All work must be performed by qualified personnel trained in the proper application, instal-

lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in 
accordance with all applicable codes and ordinances.

• To prevent serious bu r n s , the boiler must be cooled to 80˚F (27˚C) and the pressure must be 

0 psi (0 bar)

servicing

• To prevent electrical shock , turn off the electrical power before making electrical connections.

• This low water cut-off must be installed in series with all other limit and operating controls 

installed on the boiler. After installation, check for proper operation of all of the limit and 
operating controls, before leaving the site.

• We recommend that secondary (redundant) low water cut-off controls be installed on all 

steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi of 
steam pressure. At least two controls should be connected in series with the burner control 
circuit to provide safety redundancy protection should the boiler experience a low-water 
condition. Moreover, at each annual outage, the low water cut-offs should be dismantled,
inspected, cleaned, and checked for proper calibration and performance.

• To prevent serious personal injury from steam bl ow dow n , connect a drain pipe to the contro l

opening to avoid exposure to steam discharge.

• To prevent a fire, do not use this low water cut-off to switch currents over 16A, 1 Hp at

120 VAC or 8A, 1 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.

WARNING

LWCO & Pump
CONTROLLER

MODEL 150E

before

INSTRUCTION MANUAL 

MM-286B

Содержание 1575 Series

Страница 1: ...series with all other limit and operating controls installed on the boiler After installation check for proper operation of all of the limit and operating controls before leaving the site We recommen...

Страница 2: ...er level is not restored to the top probe within 3 m i nutes the pump relay will be deactivated shutting off the pump After the pump relay is deactivated normal operation is resumed Water must again d...

Страница 3: ...System Water Temperature 406 F 208 C Maximum System Water Pressure 250 psi 17 6 kg cm2 Maximum System Steam Pressure 250 psi 17 6 kg cm2 All probes in the Series 1575 units are sent from the factory p...

Страница 4: ...l water level but not lower than the lowest safe permissible water level as determined by the boiler manufacturer OR If the control will be the secondary low water fuel cut off size the steam top and...

Страница 5: ...erating probes to the desired length After cutting secure the probe rod to the electrode and lock the thread using the jamnut in the electrode sleeve Insert the probe into the chamber and tighten by h...

Страница 6: ...over Removal and Installation Procedure a To remove cover use a flathead screwdriver to loosen screws and remove the cover K b To reconnect cover slide over brackets and tighten screws using a flathea...

Страница 7: ...p Control Connect wire a from power supply to terminal H Connect wire b from neutral supply to terminal N Connect wire c from valve control circuit to terminal PNO Connect wire d from valve control ci...

Страница 8: ...PCB is too hot and the unit has shut down The unit will automatically restart when the PCB has cooled sufficiently When using the TEST button the green light will flash once per second during the time...

Страница 9: ...nit is factory set at 0 seconds To adjust turn the adjusting screw clockwise using a small flatblade screwdriver to the delay time desired Followthe bl owdown procedure found on page 11 to verify oper...

Страница 10: ...pect probes The wiring connections for the pump may not be connected properly Check wiring at terminals Burner does not turn off when water level is below longest probe The probes may be fouled with d...

Страница 11: ...ld be opened slowly The piping needs to be wa rmed up and stagant water in the drain piping needs to be pushed out Suddenly opening a blow down valve causes steam to condense which may create water ha...

Страница 12: ...nue Morton Grove Illinois 60053 Phone 847 966 3700 Fax 847 965 8379 www xyleminc com brands mcdonnellmiller McDonnell Miller is a trademark of Xylem Inc or one of its subsidiaries 2013 Xylem Inc MM 28...