• Tyco grounding hardware comes in a package that includes the grounding bolt, mounting and grounding hex
• Electrical contact is made by penetrating the anodized coating of the aluminum frame, and tightening the

mounting hex nut (come with the star washer) to the proper torque of 25lbf.in.

• Grounding wire size (6 to 12 AWG solid bare copper) should be selected and installed underneath the wire

binding bolt.

• The wire binding bolt should be tightened to the proper torque of 45lbf.in.
• The Tyco grounding bolt is only listed for use with 6 to 12 AWG bare solid copper wire.

7.3 Module wiring

All wiring should be performed, by qualified installers, in accordance with the local codes and regulations.

Modules can be connected in series to increase the operating voltage by plugging the positive plug of one module

into the negative socket of the next. Before connecting modules always ensure that the contacts are corrosion free, clean
and dry.

The product can be irreparably damaged if an array string is connected in reverse polarity to another. Always verify

the voltage and polarity of each individual string before making a parallel connection. If you measure a reversed polarity
or a difference of more than 10V between strings then check the string configuration before making the connection.

Maysun Solar modules are provided with stranded copper cables with a cross sectional area of 4mm²(0.006in²)

which are rated for 1000V DC, 90°C and are UV resistant.( For MS.**, 1500 V DC, 90°C and are UV resistant) All
other cables used to connect the DC system should have a similar (or better) specification. Maysun Solar recommend that
all cables are run inappropriate conduits and sited away from areas prone to water collection.

The maximum voltage of the system must be less than the maximum certified voltage 1000V typically (For TSM-

PE05A.**, PE14A.** , less than 1500V) and the maximum input voltage of the inverter and of the other electrical
devices installed in the system. To ensure that this is the case, the open circuit voltage of the array string needs to be
calculated at the lowest expected ambient temperature for the location. This can be done using the following formula.

System voltage=N*Voc*[ 1

λvoc (Tmin -25℃)]

N——number of modules in series
Voc— —open circuit voltage at STC (refer to product label or datasheet)
λvoc——Thermal coefficient of Voc of each module (refer to product datasheet)

Tmin— — minimum

Each module have two standards 90°C sunlight resistant output cables each terminated with plug &

play connectors. The wire type and gauge of the output cables are 1000V (For MS.**, ** which are 1500V
DC) rated PV Wire cable and are 12AWG in size. This cable is suitable for applications where wiring is
exposed to the direct sunlight. We require that all wiring and electrical connections comply with the
appropriate National Electrical Code.

The minimum and maximum outer diameters of the cable are 5 to 7mm(0.038 to 0.076in2).
For field connections, use at least 4mm2 copper wires insulated for a minimum of 90°C and sunlight

resistance with insulation designated as PV Wire.

The minimum bending radius cables should be 43mm( 1.69in).

Содержание MS M-36 Series

Страница 1: ...1 Installation Manual for Maysun Solar Monofacial PV modules For the latest version visit www maysunsolar com Version 2022 02...

Страница 2: ...Environmental Considerations 6 5 1 Climate conditions 6 5 2 Working environment 6 6 Site Selection 7 7 Mounting Instructions 7 7 1 Mounting methods 7 A Mounting with Bolts 7 B Mounting with Clamps 9 C...

Страница 3: ...l and should be installed and serviced by qualified personnel with knowledge of the mechanical and electrical requirements of the system The mechanical and electrical installation of the PV modules sh...

Страница 4: ...ment must be made in conformance with the grounding device manufacturer s instructions Common hardware items such as nuts bolts star washers lock washers and the like have not been evaluated for elect...

Страница 5: ...rank of the BOM concerned Module Fire Performance Type 1 Type 2 All series in this description All construction in this description Fire resistance rating Class C The Type 1 and or Type 2 modules with...

Страница 6: ...rical performance parameters of the module were measured under standard test conditions irradiance of 1000W m AM1 5 spectra ambient temperature of 25 C with a test uncertainty of 3 The maximum system...

Страница 7: ...nt orientations to different inverters or different MPPT if the inverter has more than one MPPT Refer to inverter manufacturers for further guidelines According to Intertek conducted IEC 61701 2011 sa...

Страница 8: ...8 www maysunsolar com...

Страница 9: ...t not deform the frame Be sure to avoid shadowing effects from the module clamps The module frame is not to be modified under any circumstances When choosing this type of clamp mounting method use at...

Страница 10: ...frame of each module has 4 7 10mm 0 28 0 39in mounting holes with specific location shown in Figure 3 Secure the module in each fixing location with an M6 bolt two flat washers a spring washer and nut...

Страница 11: ...nded in accordance with the appropriate respective National Electrical Code Proper grounding is achieved by bonding the module frame s and all metallic structural members together continuously using a...

Страница 12: ...uct Catalogue link for detailed grounding hole location and size at www maysunsolar com Method 1 Tyco grounding bolt 2058729 1 4 5 Figure 4 Tyco grounding bolt 2058729 1 1 Wire bolt and slot 3 Aluminu...

Страница 13: ...13 www maysunsolar com Figure 5 Tyco grounding bolt 1954381 2 Not applicable for the Maysun MOUNT module series 1 Wire slot available for 0 006 to 0 025in 2 Slider 3 Bolt 4 Base 5 Nut...

Страница 14: ...V resistant For MS 1500 V DC 90 C and are UV resistant All other cables used to connect the DC system should have a similar or better specification Maysun Solar recommend that all cables are run inapp...

Страница 15: ...es with an array string is typically 15A but the actual module specific rating can be found on the product label and in the product datasheet This fuse rating value also corresponds to the maximum rev...

Страница 16: ...ensure that the solar modules are clean before onset of summer Products installed at a tilt angle below 10 or which are located in particularly dusty areas are installed in landscape orientation or i...

Страница 17: ...e diodes even if they malfunction In a system using a battery blocking diodes are typically placed between the battery and the PV module output to prevent 10 Disclaimer Of Liability The installation h...

Отзывы: