Malfunctions / Breakdowns
Standards
Product standard
VDE 0160
/
DIN EN 50178:1998-04
Electronic equipment for use in power installations
EMC inspections
EN 61000-6-2:2006-03
Interference immunity
EN 61000-6-4:2007-09
Interference emission
EN 61000-6-3:2011-09
Interference emission for living area
Insulation coordination
acc. VDE 0110 / EN 60664:2008-01
Degree of pollution 2
Rated insulation voltage 63 VDC
Reliability nominal values
SN 29500, T = 60 °C / failure rates, components
EN ISO 13849-1
Disposal
Electronic Components
Products which have not been disassembled can be disposed of under Code No. 160214 (mixed materials) or components under Code No.
160216 (Code No. acc. 200/532/EC), or can be disposed of by a certified disposal firm.
Malfunction
Possible Causes
Measure
Brake does not release
No supply voltage available
Check voltage on input terminal
Brake line interrupted
Check brake supply line (check passage)
Line voltage drop on long line
Check the brake voltage
Air gap not okay
Check and adjust air gap
No signal
Brake is not permitted
Use released brake
Brake is worn
Open and clean the brake, check the air gap;
replace the brake if necessary
Incorrect input voltage polarity
Check input voltage and rotate if necessary
Error (continuous
signal)
Brake release is not recognised
Check: Brake is not permitted
Incorrect monitoring module (brake nominal voltage)
Brake drop-out is not detected
Brake is not permitted
Check the function of the monitoring module
Break voltage drop
Check network stability and reinstate it
Unit temperature over 90 °C
Check ambient temperature and, if necessary,
improve the cooling.
Warning
Coil temperature of the brake too high
Check effective coil power, ext. Temperature, friction
power
Wear
Replace rotor
Supply voltage too low
Check and, if necessary, increase supply/output
voltage of the monitoring module; check line length
Clock frequency or P
N
(coil nominal
capacity) too high
Lower clock frequency or P
N
(coil nominal capacity)
Unit temperature over 85 °C
Check ambient temperature. Check clock frequency
and P
N
.
10