Maxlogic ML-322 Скачать руководство пользователя страница 1

ML-322

COMMISSIONING, OPERATING AND MAINTENANCE MANUAL

MODEL: MAXLOGIC SERIES 

SUB MODEL: CONVENTIONAL FIRE EXTINGUISHING PANEL 

Содержание ML-322

Страница 1: ...ML 322 COMMISSIONING OPERATING AND MAINTENANCE MANUAL MODEL MAXLOGIC SERIES SUB MODEL CONVENTIONAL FIRE EXTINGUISHING PANEL...

Страница 2: ...tion steps 8 8 2 1 Fire extinguishing panel installation steps 8 9 COMMISSIONING 9 9 1 Control list before commissioning 9 9 2 The general overview of the commissioning operation 9 9 3 Cable connectio...

Страница 3: ...oard rear view 10 Figure 3 Fire extinguishing panel expansion card front view 11 Figure 4 Fault relay output jumper group doesn t connected 22 Figure5 Selecting supervise condition of the fault relay...

Страница 4: ...L 322 Maxlogic fire extinguishing panel operating manual Figure 25 Connection between panel and extinguishing status indicator units 41 3 LIST OF TABLES Table 1 Classi ications of the panel s case typ...

Страница 5: ...een performed to alarms which have been registered after last operation day If disable experiment or silence operations have been occurred and system turned back to normal operation mode This document...

Страница 6: ...on ML 322 series panel s 6 2 5 MLY 3203 Maxlogic ML 322 conv panel back TR Front side Metallic Main Board Metallic mounted front side serigraphy of the main board that is used on ML 322 series panels...

Страница 7: ...s has been disappeared Has been appeared on delay screen at the extinguishing panel as countdown Line s open or short circuit conditions has been controlled with supervised inputs First level sounder...

Страница 8: ...s on the panel when power is cut out Batteries are automatically charged 8 2 Installation steps 1 Remove the panel from box and place it on a flat surface 2 Control inside the package to check the ite...

Страница 9: ...cables on the site should not be connected 2 Zone and sounder lines must be checked that there is no any device connection between them But it is important that these lines must be located on related...

Страница 10: ...m If there is an open or short circuit condition system send fault messages Note After commissioning operation event logs must be deleted 10 SPECIFICATIONS OF THE MAIN BOARD Figure 1 Fire extinguishin...

Страница 11: ...tripod 19 Fault relay s nail group 20 Fire relay s nail group 21 Gas activate output s nail group 22 Sounder 2 output s nail group 23 Sounder 1 output s nail group 24 2nd level sounder output s nail...

Страница 12: ...0LEC GD2R 220MEC GD2R 24EC GD 220EC GD 220L GD 220LEC GD 220M GD 220MEC GDR 1224L GDR 1224LEC MaviGard electronic sounder MaviGard electronic sounder strobe red 24V MaviGard fire alarm bell 6 24V DC M...

Страница 13: ...ter extinguishing time completed on 2nd access level Depend on the default adjustments there is no any Fan Relay on the panel This function can be assigned to panel s main board by computer software o...

Страница 14: ...ble Operation Fault relay s contact has been changed and activated by any of the fault warning from system or its remote controller input and has been used to control any other system If requested fau...

Страница 15: ...r button should be pressed to enter menu screen Disable option should be selected by pressing Right Arrow Adjustments should be installed by pressing Enter button When Zone 1 switched to test operatio...

Страница 16: ...same menu 13 1 15 Manuel Extinguishing Disable Operation When manual extinguishing operation has been disabled extinguishing process does not being started by pressing Start Extinguishing button To di...

Страница 17: ...mining delay origin delay time should be adjusted on 3rd access level 13 2 2 Delay Time Adjustment for First Level Sounder First level sounder delay times can be adjusted as 30 seconds 1 minute 2 minu...

Страница 18: ...access level Enter button should be pressed to enter menu screen Enable selection has been selected by Right Arrow button Adjustments should be installed by pressing Enter button Disable selection at...

Страница 19: ...selected Gas Output Activated LED is flashes and Gas Activated output stays at the normal condition unless Gas Activate input has not been trigged If it is trigged Gas Output Activated LED is permane...

Страница 20: ...2 17 Determining Delay Source of the Zone 3 for First Level Sounder Output Delay origin should be selected to perform delay operation at Zone 3 To select this feature Zone 3 Delay Device menu screen s...

Страница 21: ...ght Arrow button If Extinguishing Output desires to stay be activated unit reset this feature should be selected 13 2 22 Date Adjustment To keep event of the system in order the date must be adjusted...

Страница 22: ...3 and Zone 4 inputs on the main board Any other output function cannot be assigned to Extinguishing Output Fire Signal Output and Fault Signal Output outputs on the main board Outputs supervised condi...

Страница 23: ...g manual Figure5 Selecting supervise condition of the fault relay output as No Example The adjustment has been shown in 19th fault relay of Figure 2 Fire extinguishing panel main board rear view for e...

Страница 24: ...isabled device s open close condition 14 1 5 Disabling Device Abnormal Input This is the input that is used to connect activated output which is not exactly open or close 14 1 6 Silence Remote Alarm A...

Страница 25: ...nds Any other cases ON OFF When extinguishing has been disabled Any other cases ON OFF When extinguishing has been delayed Any other cases ON OFF When extinguishing has been cancelled Any other cases...

Страница 26: ...First Level Output 14 2 24 Programmable Relay Programmable relay s condition and activity condition can be programmed at PC software At the programmable relay inputs fire fault and disable conditions...

Страница 27: ...d printer output does not connected 5 Isounders It is the maximum total current value of S1 S2 and S3 sounder outputs The connected load value of the outputs is found by addition operation Isounder Is...

Страница 28: ...rformed or monitored by resistance value which can be adjusted by Extinguishing Monitoring tripod 1 pc of valve or up to 4 pcs of activator can be connected 2 2 ohm 2 5 W end of line resistance should...

Страница 29: ...shing Sounder Extinguishing Delay Condition 1s ON 1s OFF During extinguishing operation holds on 1s ON 2s OFF Release Condition ON After Extinguishing Condition Unpredicted Release Condition Any other...

Страница 30: ...sful Ext Detection menu step during After Extinguishing condition If Enable feature has been selected Gas Activated output only activates Gas Activated input has been trigged If Disable feature has be...

Страница 31: ...s a device as a controller relay a contactor must be placed Relay outputs may damages as a result of not using contactor on a high current draw application this condition it not under guarantee 16 6 S...

Страница 32: ...ers Zone 1 and Zone 2 have been used to initiate extinguish ing Zone 3 and Zone 4 have been used to transmit fire alarm The zones which will be assigned for to initiate extinguishing operation can be...

Страница 33: ...has been trigged or if a fault may be occurred at this input the countdown has been stopped When Reset input has been turned back to its normal condition countdown will be continues When Reset input...

Страница 34: ...condition switch input Figure 23 Extinguishing condition switch input This input has been used to select extinguishing mode remotely Mode selection operation has been performed by extinguishing switc...

Страница 35: ...ondition Pre function condition This is a fire alarm condition for the initiating operation of the extinguishing which panel received fire alarm from any of the zone during Automatic Manual mode Funct...

Страница 36: ...ly illuminating LED they keeps their conditions Internal buzzer sounds System fault messages will be displayed on the LCD But a system fault that block this may occurs there fore the true message does...

Страница 37: ...er line fault conditions Sounder Fault Disable LED has been flashes and if sounder disabled it illuminates permanently When fault condition has been disappeared or disabled sounder has been enabled ag...

Страница 38: ...led has been flashed If any of the detection zone has been disabled or test operation is performing fault LED illuminates permanently NAME 0 25s ON 0 25s OFF ON Activity condition Pro activity conditi...

Страница 39: ...ndition microprocessor reset button should be used System Fault LED has been illuminated when there is a problem for the system operation At this condition microproces sor reset button has been used t...

Страница 40: ...ble number of the extinguishing status indicator units has been displayed on the screen Displayed message s type has been shown at the following figure The following message shows that there is one av...

Страница 41: ...Reset Disabled Disabled Enable Enable key Alarm Silenced Extinguishant Control Panel Delay On System Fault Power Fault FIRE FIRE FAULT EXTINGUISHANT RELEASE PULL DOWN PUSH BUTTON EXTINGUISHANT EXTINGU...

Страница 42: ...panel 4 Control console s tests a Controlling console s LED and display tests b Controlling access level entries c Simulating detection zone alarm activating operation by panel d Simulating detection...

Страница 43: ...nical service personal have been trained for the unreachable ones c Fire alarm buttons activated and controlled d 3rd party system s connections at input modules of the fire detection system have been...

Страница 44: ...Page 44 53 KK 642 041 Rev No 1 01 08 12 ML 322 Maxlogic fire extinguishing panel operating manual ANNEX ML 321 SERIES PANEL STRUCTURE...

Страница 45: ...Page 45 53 KK 642 041 Rev No 1 01 08 12 ML 322 Maxlogic fire extinguishing panel operating manual ANNEX ML 322 SERIES PANEL STRUCTURE...

Страница 46: ...e event source s address I N 0 3 F L T 0 0 3 0 0 5 F a u l t O C Show the number of the event depend on the event group Show the total event number depend on the event group Describe event SC Short ci...

Страница 47: ...ire Relay Fault Relay Zone 1 Zone 2 Zone 3 Zone 4 Zone 1 Test Zone 2 Test Zone 3 Test Zone 4 Test Low Pressure Input Manuel Extinguishing Extinguishing System Enable Disable Active Passive Enable Disa...

Страница 48: ...elay Zone 2 Delay Zone 3 Delay Zone 4 Delay Zone 1 Unlocked Zone 2 Unlocked Zone 3 Unlocked Zone 4 Unlocked Ground Fault Unsuccesful Ext Det Delay Reset Man Ext Abort Zone 1 Dly Device Enable Disable...

Страница 49: ...ogic fire extinguishing panel operating manual All All Detector No Delay Zone 2 Dly Device Zone 3 Dly Device Zone 4 Dly Device Res Eng Time Ext Delay No Delay Cal Point All Detector No Delay Cal Point...

Страница 50: ...53 KK 642 041 Rev No 1 01 08 12 ML 322 Maxlogic fire extinguishing panel operating manual Date Time Print Event Log Delete Event Log Abort Type Abort Res and Abort xx xx xx xx xx 30 300 sec Permenant...

Страница 51: ...ne 1 Non latching Zone 2 Non latch Zone 2 Non latching Zone 3 Non latch Zone 3 Non latching Zone 4 Non latch Zone 4 Non latching Unsucc Ext Det Unsuccessful Extinguishing Detection Delay Reset Delay R...

Страница 52: ...Grey tone RAL 7015 white panel front side Ambient Condition Specifications Operating Temperature Interval Operating Humidity Interval 5 C 50 C 0 95 uncondensed Battery Specifications Battery Battery...

Страница 53: ...as Activated Output Cable specification for Gas Activated Output Fire Relay Fault Relay Cable specification for relay outputs Fire Signal Output Fault signal Output Cable specifications for signal out...