EXA Modulating E40, E50, E60 Valve Series

Figure 1: EXA Modulating Valve Series

1

© 2019 Maxitrol Company, All Rights Reserved.

PATENT PENDING

The  E40(H),  E50(H),  E60(H)  modulating  valves  are  highly 

accurate and precise modulating control valves (see figure 1). 

EXA  valves  provide  repeatable  process  control  with  minimal 

hysteresis throughout the entire range of modulation.

The  EXA  modulation  system’s  high  fire  setting  and  low  fire 

setting are user programmable.

The EXA  modulating valve series has a built-in digital controller 

that provides a seamless interface with a process controller. 
The  valve  has  two  (2)  buttons  and  a  communication  LED  for 

the user interface. The buttons are used to set high and low fire 

settings (see figure 4, page 4). 
The valve has full open and full close (not gas tight) mechanical 

limits. The user can program settings that are within the valve’s 

mechanical limits. This added dimension for sizing and applying 

the valve is an important feature. It allows the valve to be set 

up for an entirely different net output characteristic (dependent 

upon supply pressure) (see table 1, page 2).
There are six (6) electrical connections on the EXA valve. Two 

(2) are for power, two (2) are for the control signal, and two (2) 

are for position feedback (see figure 2, page 2).

Disconnect  power  before  installation  to  prevent  electrical 

shock, equipment or control damage.

WHAT TO DO IF YOU SMELL GAS 

1. Do not operate any appliance.

2. Do not touch any electrical switch; do not use any 

phone in your building.

3. Immediately evacuate the area and contact the gas 

supplier. Follow the gas supplier’s instructions.

4. If you cannot reach the gas supplier, call the fire 

department.

This control 

must

  be  installed  and  operated 

strictly

 in 

accordance  with  the  instructions  of  the  OEM  and  with 

all  applicable  government  codes  and  regulations,  e.g. 

plumbing,  mechanical,  and  electrical  codes  and  practices. 

These  instructions  do  not  supersede  OEM’s  installation  or 

operating instructions.  

© 2019 Maxitrol

Maximum Inlet Pressure: 

5 psig 

NOTE: 

Up to 10 psig available, consult Maxitrol Company.

Power Requirements: 

24 VAC/DC  +/- 10% 50/60 hz

NOTE: 

The E40H, 50H, 60H use half-wave rectifiers. 

 

When using a single transformer for powering the E40H, 

50H,  60H  and  devices  with  half-wave  rectifiers,  the 

common for each must be connected to the same leg 

of the transformer. Control signal devices with full-wave 

bridge rectifiers require a separate transformer. 

 

See “

Power Supply Compatibility

” bulletin.

Maximum Current Draw:

 200mA

Temperature Limits:

 -40ºF to 150ºF operating

Control Signal (user selectable): 

0-10 VDC, 2-10 VDC, 

0-20 mA, 4-20 mA; 100KOhm Input Impedance

Mounting: 

Multipoise

Gases: 

Suitable for natural, manufactured, mixed gases, 

liquefied petroleum gases, and LP gas-air mixtures.

Certifications:

 

EMC (EN 61000:2001)

 

Immunity (EN 61000-6-2:2001)

 

Emissions (EN 61000-6-4:2001)

 

UL Recognized

 

Enclosure: 

IP40

Electrical Connection: 

UL310

Sizes: 

  E40: 3/8”, 1/2” NPT or Rp ISO 7-1

 

E50: 1/2”, 3/4” NPT or Rp ISO 7-1

 

E60: 3/4”, 1” NPT or Rp ISO 7-1