maximal Maximal3DV Скачать руководство пользователя страница 1

Rev. 061307

More than just power.

TM

Access Power Controllers

Installation Guide

Models Include:

Maximal3DV

  -  12VDC @ 5A or 24VDC @ 5.4A.
  -  Sixteen (16) PTC protected outputs.

Maximal5DV

  -  12VDC @ 9A.
  -  Sixteen (16) PTC protected outputs.

Maximal7DV

  -  24VDC @ 9.4A.
  -  Sixteen (16) PTC protected outputs.

Содержание Maximal3DV

Страница 1: ...M Access Power Controllers Installation Guide Models Include Maximal3DV 12VDC 5A or 24VDC 5 4A Sixteen 16 PTC protected outputs Maximal5DV 12VDC 9A Sixteen 16 PTC protected outputs Maximal7DV 24VDC 9 4A Sixteen 16 PTC protected outputs ...

Страница 2: ... Controller Terminal Identification pg 6 Power Supply Board Stand by Battery Specifications pg 6 Power Supply Board Output Voltage Settings pg 7 Access Power Controller Typical Application Diagram for each ACM8CB pg 7 Maximal3DV and Maximal5DV Battery Hookup and Tamper Switch Installation pg 8 Maximal7DV Battery Hookup and Tamper Switch Installation pg 9 NEC Power Limited Wiring Requirements for M...

Страница 3: ...teen 16 normally open NO dry trigger inputs b Sixteen 16 open collector inputs c Any combination of the above Sixteen 16 unswitched filtered and electronically regulated aux power outputs outputs are rated 2 5A Red LEDs on ACM8CB board indicate individual outputs are triggered relays energized Fire Alarm disconnect latching or non latching is individually selectable for any or all of the sixteen 1...

Страница 4: ...unit before connecting any devices to ensure proper operation Improper or high voltage will damage these devices 5 Output options Fig 2 pg 7 The unit will provide any combination of Fail Safe and or Fail Secure switched power outputs a Fail Safe Switched Power outputs For Fail Safe operation connect the positive input of the access control devices to terminal marked NC Connect the negative input o...

Страница 5: ... for the proper operation as follows FACP Supervision To ensure proper connection and operation of the Fire Alarm disconnect hookup Please follow the appropriate procedure below Normally Open Input Placing a short between terminals marked T and INP will trigger the Fire Alarm Disconnect Remove the short to reset Normally Closed Input Remove the wire from terminal marked INP will trigger the Fire A...

Страница 6: ...series for 24VDC operation Fig 4 pg 9 Access Power Controller Terminal Identification Terminal Legend Function Description Power 12VDC or 24VDC input from power supply board Control Not applicable TRIGGER INPUT 1 INPUT 8 IN GND From normally open and or open collector sink trigger inputs request to exit buttons exit pir s etc OUTPUT 1 OUTPUT 8 NC C NO COM 12VDC to 24VDC trigger controlled outputs ...

Страница 7: ...cation corresponding fuse F8 must be removed Keypad NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5...

Страница 8: ...2 TRG NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4 O N 1 2 3 4 O N LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN ...

Страница 9: ...C C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4 O N 1 2 3 4 O N LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG NC C NO COM OUTPUT 3 N...

Страница 10: ... require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 5a External Jacketed Shield Incorrect Wi...

Страница 11: ... require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 6a External Jacketed Shield Incorrect Wi...

Страница 12: ... require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 7a External Jacketed Shield Incorrect Wi...

Страница 13: ...CE FACP Hook Up Diagrams Fig 8 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition N O TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 9 Normally Open Non Latching FACP trigger input N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG NO C NC Fig 10 Normally Open FACP Latching trigger input with reset ...

Страница 14: ...llers PTC JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 11 Normally Closed Non Latching FACP trigger input N C TRIGGER INPUT N C RESET SWITCH JUMPER TRG Fig 12 Normally Closed Latching FACP trigger input with reset FACP Hook Up Diagrams cont d ...

Страница 15: ...Maximal3DV Maximal5DV Maximal7DV Access Power Controllers PTC 15 Notes ...

Страница 16: ...50 8mm 2 50 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 26 660 4mm 26 660 4mm 7 5 190 5mm 5 127mm 26 660 4mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 81...

Отзывы: