PARAMETERS
www.maxcessintl.com
DLCA NET-S1
MI 850A374 1 A
Page 38 of 67
7.6
Calibrate the analog outputs (not normally changed)
These parameters set the offset and gain for the analog outputs to calibrate the outputs to
real volts or real current. The parameters compensate for component tolerances on each
DLCA NET-S1. These parameters are calibrated at the factory and are not reset by the
power-up function reset parameters to default.
If these need to be changed, connect a voltmeter or current meter (as appropriate to the
output that is being calibrated) and adjust the number until the voltage or current reads the
proper value.
Parameter
Description
Range
Output 1
CO.11
Sets the 0 to 10V output to 0%.
Change the value until the meter reads 0.00 volts.
{0, 9999}
CO.12
Sets the 0 to 10V output to 100%
Change the value until the meter reads 10.00 volts.
{0, 9999}
CO.13
Sets the 0 to 20mA output to 0%.
Change the value until the meter reads 0.00 mA.
{0, 9999}
CO.14
Sets the 0 to 20mA output to 100%.
Change the value until the meter reads 20.00 mA,
{0, 9999}
Output 2
CO.21
Sets the 0 to 10V output to 0%.
Change the value until the meter reads 0.00 volts.
{0, 9999}
CO.22
Sets the 0 to 10V output to 100%
Change the value until the meter reads 10.00 volts.
{0, 9999}
CO.23
Sets the 0 to 20mA output to 0%.
Change the value until the meter reads 0.00 mA.
{0, 9999}
CO.24
Sets the 0 to 20mA output to 100%.
Change the value until the meter reads 20.00 mA,
{0, 9999}
Meter Output
CO.41
Sets the meter output 1 to 0%.
Change the value until the meter reads 0.00 mA.
{0, 9999}
CO.42
Sets the meter output 1 to 100%.
Change the value until the meter reads 1.00 mA.
{0, 9999}
CO.43
Sets the meter output 2 to 0%.
Change the value until the meter reads 0.00 mA
{0, 9999}
CO.44
Sets the meter output 2 to 100%.
Change the value until the meter reads 1.00 mA
{0, 9999}