i-HWAK V4 

 

Chillers and inverter air / water heat pumps with axial fans

 

10

 

5

 

TECHNICAL CHARACTERISTICS 

The i-HWAK V4 water chillers and heat pumps series are designed for applications in residential and commercial areas, These units 
are extremely versatile and can operate in heat pump mode with the ability of producing hot water at a temperature of 58°C for 
environmental heating and sanitary applications. The INVERTER compressor with brushless DC motor technology, matched with 
electronic  expansion  valve,  pump  and  variable  speed  blower  are  generally  used  for  optimizing  the  power  consumption  and 
efficient operation of the refrigerating components. 

5.1

 

FRAME 

All the unist of i-HWAK V4 series  are made up of hot-galvanised thick sheet metal, painted with polyurethane powder enamels at 
180°C to ensure the best resistance against atmospheric agents. The frame is self-supporting with removable panels. All screws 
and rivets for outdoor installations are in galvanized steel. 

5.2

 

REFRIGERANT CIRCUIT 

The refrigerant gas used in these units is R410A. The refrigerant circuit has been manufactured by means of international primary 
brands components and according to the UNI EN 13134 Rule concerning welding procedures. The refrigerant  circuit includes: 4 
way reverse cycle valve, electronic expansion valve, liquid separator, liquid receiver, valves for maintenance and control, pressure 
safety device, pressure transducers to accurately adjust the evaporating and condensing pressures, filters for throttling valve to 
avoid its clogging. 

5.3

 

COMPRESSORS 

The installed DC inverter compressors are rotary hermetic twin rotary type designed to be used with R410 refrigerant. 
The compressors are mounted in a separate chamber, isolated from the air stream in order to reduce the noise, and are equipped 
with  crankcase  heater,  In  order  to  avoid  the  oil  dilution  which  may  cause  seizure  of  the  compressor.  The  crankcase  heater 
operates when the compressor remains off for at least 30 minutes and if the discharge temperature is below 20°C (with hysteresis 
of 2.0°C). When the compressor restarts, the crankcase heater will stop operation. The crankcase heater works even if the unit is 
in shut off mode, which will protect the compressor from restartup failure. 
We recommend you to turn ON the unit and to put it in standby mode at least for 6 hours before starting the operation, especially 
if the system has been completely turned off for a period of time. 
The checking of the compressors is possible through removing the frontal and lateral panels of the unit allowing easy maintenance 
of the compressors even when the unit is operation. 

5.4

 

AIR SIDE EXCHANGERS 

The  air  side  exchangers  are  made  up  of  copper  pipes  and  aluminium  fins.  The  diameter  of  the  copper  pipes  is  9.52mm  for  the 
model 09 and 5/16” for the other models 12 and 15, the thickness of the aluminium fins is 0,1mm. The tubes are mechanically 
expanded into the aluminium fins to improve the heat exchange factor. The geometry of these condensers guarantee a  low air 
side pressure drop and, then, the use of low rotation (and low noise emission) fans. 

5.5

 

FANS 

The fans are axial type with aluminium aerofoil blades. They are statically and dynamically balanced and supplied complete of the 
safety fan guard according  to the CEI EN 60335-2-80 Rule (safety for electrical apparatus of domestic and similar use). They are 
mounted  on  the  unit  frame  by  interposition  of  rubber  vibration  dampers.  The  electric  motors  are  all  brushless  DC  type  with  8 
poles (about 200/1000 rpm). The motors are directly driven with an integrated thermal overload protection. The protection class 
of the motors is IP X44. 

5.6

 

USER SIDE HEAT EXCHANGERS 

The  user  side  heat  exchangers  are  made  up  of  AISI  304  stainless  steel  braze-welded  plates  type.  The  user  heat  exchangers  are 
factory insulated with flexible close cell material and can be equipped with antifreeze heater (KA optional). Each heat exchanger is 
provided with a temperature sensor working as antifreeze protection that activates the circulator, even in the case when the unit 
is turned off when the conditions set in the controller have been occurred. 

5.7

 

ELECTRIC BOX 

The  electric  box  is  manufactured  according  to  the  current  European  Union  laws.  The  accessibility  to  the  board  is  possible  after 
removing the cover panel of the unit using proper tools. The protection degree is IP24. The terminal board is supplied with voltage 
free  contacts  for  remote  ON-OFF,  winter/summer  change  over,  auxiliary  heater,  sanitary  water  temperature  sensor  control  of 
external 3-way valve and free contacts for remote control panel and for the management of the dual set point of operation. 

5.8

 

CONTROL SYSTEM 

All  the  units  of  i-HWAK  V4  series  are  standard  supplied  with  a  microprocessor  adopting  an  overheating  control  logic  program 
through the electronic expansion valve which is driven by the pressure transducers signals. The microprocessor is also capable of 
controlling the following functions: water temperature regulation, antifreeze protection, compressors’ time setting,  compressor 
automatic  starting  sequence,  alarm  reset,  alarm  management  and  operating  LED.  Upon  request,  the  microprocessor  can  be 
connected to a BMS remote control system and to the simpler HNS system with our terminal units. The control system together 
with  the  INVERTER  technology  and  the  on  board  sensors  continuously  monitor  and  adapt  the  performance  of  the  inverter 

Содержание i-HWAK V4 06

Страница 1: ...T I O N I N G A47 USER S INSTALLER S MANUAL Serie Series Serie S rie Emissione Edition Au sgabeIssue Controller for i HWAK V4 06 14 T 16T 03 2017 Catalogo Catalogue Katalog Brochure Sostituisce Supers...

Страница 2: ...124H7820 01 Serie Series Serie Serie S rie USER S AND INSTALLER S MANUAL FOR CHILLERS AND INVERTER AIR WATER HEAT PUMPS WITH AXIAL FANS Possible wasted electrical or electronic devices products should...

Страница 3: ...rmativa PED 2014 68 UE Riferimento Art I paragrafo 2 punto f 2 Harmonized standards applied to designing and manufacture UNI EN 378 1 UNI EN378 2 UNI EN 12735 1 Norme armonizzate applicate alla proget...

Страница 4: ...11 6 AVAILABLE VERSIONS 11 6 1 OPTIONAL ACCESSORIES 12 7 INSTALLATION 13 7 1 GENERALITY 13 7 2 LIFTING AND HANDLING 13 7 3 LOCATION AND MINIMUM TECHNICAL CLEARANCES 13 7 4 HYDRAULIC CONNECTIONS 14 7 4...

Страница 5: ...DIMENSIONS 27 17 1 MODELS I HWAK V4 06 08 27 17 2 MODELS I HWAK V4 10 12 27 17 3 MODELS I HWAK V4 14 14T 16T 28 17 4 INTERNAL PARTS OF THE UNIT 28 17 4 1 Mod i HWAK V4 06 08 28 17 4 2 Mod i HWAK V4 10...

Страница 6: ...The company therefore is not constrained to update the manuals for previous versions of machines It s recommended that the user must follow the instructions contained in this booklet especially those...

Страница 7: ...for the performance of their tasks in safety Operators have to know how to use personal protective devices and have to know the accident prevention guidelines contained in national and international l...

Страница 8: ...and maintaining the i HWAK V4 units use the following personal protective equipment Protective clothing Maintenance men and operators have to wear protective clothing that complies with the basic safe...

Страница 9: ...rameters AEL 8 h e 12 h TWA 1000ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator apparatus The vapors are...

Страница 10: ...the unit is operation 5 4 AIR SIDE EXCHANGERS The air side exchangers are made up of copper pipes and aluminium fins The diameter of the copper pipes is 9 52mm for the model 09 and 5 16 for the other...

Страница 11: ...trol is managed by the microprocessor and is necessary for optimizing the pressure of evaporation condensation during summer winter operation in order to allow proper running of the unit 6 AVAILABLE V...

Страница 12: ...oint of operation for the plant side IMPORTANT NOTE ONLY THE OPTIONAL ACCESSORIES THAT ARE NOT INSTALLED IN THE FACTORY CAN BE REQUIRED AFTER THE ORDER OF THE UNIT WHILE THE FACTORY INSTALLED ACCESSOR...

Страница 13: ...NEL Before any operation on the unit make sure the power supply is disconnected WARNING MOVING PARTS RISK OF DEATH Disconnect the power supply and ensure that the fan is stopped before opening the fro...

Страница 14: ...ally All units are standard supplied with the water flow switch factory installed Should the water flow switch be altered removed or should the water filter not be installed on the unit the warranty w...

Страница 15: ...valve G Safety valve D High efficiency circulating pump with H Pressure gauge During the operations of charging topping up the plugs of the air vent valve must be partially unscrewed in order to allow...

Страница 16: ...LET TEMPERATURE OUT WATER OUTLET TEMPERATURE CP CAPILLARY 7 7 REFRIGERANT DIAGRAM OF 14 16 IN OUT DT OS ST LP HP 4WV LR EEV FL FL FL C CLS Pr PV Pr PV CP SE M M P C COMPRESSOR CLS COMPRESSOR LIQUID SE...

Страница 17: ...unit close to the side where the controller is positioned To get access to the terminal block please see the indications reported in the paragraph 7 8 2 The wiring to the terminal block has to be rea...

Страница 18: ...is only one fixing screw in the controller s lateral part of the unit 2 Remove the screws connecting the cover plate of the electric box then proceed to connect wire to the terminal block 3 Insert the...

Страница 19: ...s installed upstream of the system If the temperature drops below 0 C there is serious danger of frost add a mixture of water and glycol in the plant otherwise drain the hydraulic circuits of the plan...

Страница 20: ...ds in the atmosphere They have to be collected and delivered to the seller or to proper gathering points at the end of their operating life Refrigerant R410A is mentioned among controlled substances a...

Страница 21: ...sign Pressure high low MPa 4 2 2 7 4 2 2 7 4 2 2 7 4 2 2 7 Circulator Water flow rate 3 m3 h 1 13 1 38 1 72 2 08 Available head pressure 3 kPa 44 6 34 5 39 4 34 2 Rated power input 3 kW 0 045 0 045 0...

Страница 22: ...1405 x 455 1060 x 1405 x 455 Max Packing dimensions LxAxP 9 mm 1125 x 1581 x 515 1125 x 1581 x 515 Operating weight kg 119 130 Net Gross weight kg 115 5 126 126 3 137 Prestazioni riferite alle seguen...

Страница 23: ...thout head losses of the hydronic kit The optimal operating point is shown on each curve under the specified conditions at the apex 3 p 21 The circuit s plant must be designed so as to ensure the nomi...

Страница 24: ...i HWAK V4 Chillers and inverter air water heat pumps with axial fans 24...

Страница 25: ...this case contact our company for the feasibility study and evaluation of changes to be made according to your requests The maximum temperature that can be maintained at the outlet of the evaporator...

Страница 26: ...ers and inverter air water heat pumps with axial fans 26 Below the operation limits are graphed in the case of air conditioning and sanitary hot water production WATER CHILLER HEAT PUMP MODES DOMESTIC...

Страница 27: ...ate correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation without glycol The wat...

Страница 28: ...ew 1 from the side panel for separating the side panel from the front panel Detail A 3 Sequentially twist off the screws number 5 6 7 in order to move shift slightly the front panel and gain access to...

Страница 29: ...the side panel pull the panel forward to remove it in order to loose the hooking tab on the basement indicated as C in the detail B and remove it 17 4 3 Mod i HWAK V4 14 14T 16T 1 Remove the cover twi...

Страница 30: ...62 INVERTER U V W L2 L1 AC L AC N PE INV 43 43 46 46 L in N in L out N out EMI 1 pH QF F1 21 14 16 18 TO 01 F 5 01 K 15 TO 01 F 5 01 K 15 44 24 22 8 10 5 35 48 48 93 22 23 24 93 23 17 16 15 14 TO 02...

Страница 31: ...DO4 DO3N CEH1 A B 80 R3 A B R1 A B R2 A B 78 Front heating plate Rear heating plate e l b a c g n i t a e h m o t t o B 78 N2 76 76 67 66 58 N1 57 Auxiliary heater 230 V 5A Boiler heater 230 V 5A San...

Страница 32: ...ingresso Descrizione Description Component Componente HP LP OUT ST IN Indice Sonde Probe index Sonda temperatura esterna Sonda temperatura scarico compressori EXT DT Water inlet temperature probe Suc...

Страница 33: ...15 17 16 17 8 7 8 Coil RL1 37 37 112 112 12V 0V 32 48 C1 U V W GND 63 20 7 10 11 10 11 12 19 TO 01 A 13 01 G 11 TO 01 A 13 01 G 11 TO 02 H 7 TO 02 H 7 TO 01 L 11 01 G 11 TO 01 L 11 01 F 11 TO 02 M 10...

Страница 34: ...102 41 01 H 11 01 G 11 39 N DI Of Rev 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 A B C D E F G H I J K L M 03 02 2017 2 3 0 0 03 02 2017 AB Emissione MP AB 14 kW 1Ph Schema elettrico funzional...

Страница 35: ...Component Fusibile 2 x 32A 10 3x38 Fuse 2 x 32A 10 3x38 Indice Fusibili Fuse index Resistenza compressore Compressor heater Compressore Compressor Ventilatore Fan motor Trasformatore Transformer Desc...

Страница 36: ...10 11 13 14 15 112 39 42 43 43 13 15 60 58 65 75 73 74 L N P1 TO 02 H 7 TO 02 H 7 02 K 8 27 L N TB1 33 35 35 56 53 104 55 51 32 31 55 54 55 53 TO 01 K 8 01 K 19 TO 01 K 8 01 L 19 TO 02 M 10 TO 02 J 2...

Страница 37: ...71 01 K 19 01 L 19 116 106 01 L 19 41 01 L 19 104 N DI Of Rev 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 A B C D E F G H I J K L M 03 02 2017 2 3 0 0 03 02 2017 AB Emissione MP AB 14 16 kW Sc...

Страница 38: ...mponent Componente F1 CB1 TF1 M1 M2 C1 CEH1 Componente Component Controllo bordo macchina Control board Indice Componenti Component index Description Descrizione Trasformatore Transformer Ventilatore...

Страница 39: ...l 21 HANDBOOK FOR CONFIGURATIONS OF SOME INSTALLATIONS If you need more information about the possible configurations there is a handbook that is a technical book containing a series of recommended dr...

Страница 40: ...a nufacturer reserves the right to modify the data whenever it is considered necessary Via S Giuseppe Lavoratore 24 37040 Arcole Verona Italy Tel 39 045 76 36 585 r a Fax 39 045 76 36 551 r a www maxa...

Отзывы: