Chillers and Inverter Air/Water heat pumps with axial fan

additional resource for heating in case the compressor cannot meet the set in a reasonable time. The resistor controller only operates in heating 

mode and if r10 = 1.

To define how the integration resistors are to be activated, parameter r24 must be set:

• 

r24 = 0 for integration resisitors not used;

• 

r24 = 1 for use of system integration resisitor;

• 

r24 = 2 for use of sanitary integration resisitance;

• 

r24 = 3 for use of both the system integration resistor and the sanitary integration resistor.

21.1 

SYSTEM RESISTENCE

The system resistance must be connected to the digital output DO2E and can be configured by setting parameter H87 = 22.

If the regulation temperature remains lower than the hot water set-point Hea – r11 (°C) the integration resistor is activated according to the 

operation of the machine in the combined or replacement bands.

The resistor is also activated if the control temperature remains below the water set-point Hea – r11 (°C) and the machine is in lockout due to 

the intervention of an alarm. It switches off when the machine exits the alarm block.

Setting r21 = 1, during the defrost cycle, if required (temperature lower than Hea - r11), the system resistor is activated without waiting for the 

time defined by r12.

The resistor switches off when the set-point is reached (also taking into account any offset set with parameters r29 or r30).

Parameter

VALUE

Function

H87

22

System integration resistance

r10

1

Enabling of system resistors

r11

5 (default)

Delta resistances in system integration (in tenths of °C)

r12

10 (default)

System integration activation delay (in minutes)

r21

1

Enabling resistors during defrosting

r24

1/3

Type of use resistors

21.2 

SANITARY RESISTANCE

This function can be activated as an alternative to the system integration resistance. The DHW resistance must be connected to digital output 

DO3 and can be configured by setting parameter H88 = 26, in addition the DHW function must be active.

The resistance is activated if the production of domestic hot water lasts longer than r16 (minutes) or if the machine goes into lockout due to 

the intervention of an alarm. It switches off when the machine finishes DHW production (also taking into account any offset on the set-point set 

with parameter r31).

Parameter

VALUE

Function

H88

26

DHW integration resistor

r15

1

Enabling of DHW resistors

r16

10 (default)

Sanitary integration activation delay (in minutes)

r24

2/3

Type of use of resistance

21.3 

INDIVIDUAL SYSTEM/HEALTH INTEGRATION RESISTENCE

Configuring the DHW resistance it is also possible to use it as a system resistor, by setting the parameter 

r15 = 2

 and 

r24 = 3

.

In this way, in the event of a request for system integration, the resistance declared as DHW integration is activated, thus making it possible to 

have a single integration resistance for the system, DHW and defrosting.

21.4 

INTEGRATION RESISTANCE SELECTION MODE

The resistors can be activated simultaneously if 

r14 = 0

 (default), otherwise the priority of the order of activation of the system-side and DHW-

side integration resistors can be set, in particular the configurations are:

• 

r14 = 1 for resistance activation in exclusion of each other;

• 

r20 = 0 for system priority (the domestic heating element is activated only if the system-side thermoregulation is satisfied);

• 

r20 = 1 sanitary priority (the system resistor is activated only if the thermoregulation on the sanitary side is satisfied).

21.5 

CIRCULATOR MANAGEMENT WITH ACTIVE RESISTANCE

The circulator of the heat pump can be activated when the plant and/or DHW integrations resistences are active with the compressors not run

-

ning (by substitution, by alarm or by integration in bracket II or III):

• 

r33 = 0 for activation on request of the compressors or for any boiler request.

• 

r33 = 1 for activation with system resistance active.

• 

r33 = 2 for activation with sanitary element active.

• 

r33 = 3 for activation with system or sanitary resistor active.

The circulator switched off after post-pumping (P02).

21.6 

BOILER ENABLING

This function can be activated as an alternative to the SANITARY RESISTANCE function.

This is an additional resource to enable the boiler in integration or substitution of the heat pump. The relative digital output for enabling the 

boiler is DO7, it can be configured by setting parameter H88= 29.

Define the mode of use by setting parameter r23:

• 

r23 = 0 (default) for boiler not used (priority of resistor intervention);

Содержание i-HPV5H 0140

Страница 1: ...er any form of the texts and of the figures contained in this manual This manual is a translation from the official italian language version For reasons of environmental respect the Company will not p...

Страница 2: ...B First emission Rev Date Compiled Approved Note Code Serie MCO01080100001 Chillers and inverter Air Water heat pumps with axial fans Controllo per i HPV5 Chillers and Inverter Air Water heat pumps w...

Страница 3: ...NU PAR 10 4 9 OPERATING HOURS MENU OHR 10 4 10 LOG MENU HIST 10 4 11 FIRWARE VERSION MENU FIR 10 4 12 USB MENU USB 10 4 12 1 FIRMWARE UPDATE UPdF 10 4 12 2 PARAMETERS UPDATE UPPA 10 5 SYSTEM RESOURCES...

Страница 4: ...YSTEM HEALTH INTEGRATION RESISTENCE 19 21 4 INTEGRATION RESISTANCE SELECTION MODE 19 21 5 CIRCULATOR MANAGEMENT WITH ACTIVE RESISTANCE 19 21 6 BOILER ENABLING 19 21 7 LOGIC OF INTEGRATION HEATERS AND...

Страница 5: ...5 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 24 13 LACK OF VOLTAGE 28 24 14 UTILITIES BLOCK ALARM TABLE 28 25 MODBUS VARIABLES 29...

Страница 6: ...on due to dangerous electrical voltage Indicates important information that the operator has to follow in order to guarantee the correct operation of the unit in complete safety Also indicates some ge...

Страница 7: ...tivated and or modified at the same time Different values from the default values can compromise the correct operation of the unit in case of doubt on the value to set contact the company Only authori...

Страница 8: ...e to a higher menu or to increase the parameter value DOWN key allows to move to a lower menu or to decrease the parameter value 4 1 2 LED Cooling mode LED is on if COOL or COOL SAN mode is selected H...

Страница 9: ...0 C San2 Second sanitary setpoin 48 0 25 60 C Coo2 Second Summer setpoint 18 0 Coo 25 C Hea2 Second Winter setpoint 35 0 25 Hea C If sanitary function is enabled see par 12 4 4 PASSWORD MENU PSS Enter...

Страница 10: ...can read firmware version uEr revision rEu and sub revision SUb 4 12 USB MENU USB This menu appears after entering the installer password only if a USB key containing the relevant update files is con...

Страница 11: ...ion by default par 13 1 DO7 H85 XP 10 1 N XP 10 2 fase 6 HDW valve control Voltage output 230Vac 50Hz 2A AC1 see paragraph 12 Modbus RTU RS485 XC 1 1 GND XC 2 1 R XC 2 2 R Factory enabled with CM acce...

Страница 12: ...nt set point will be set Coo Hea b15 2 With input at 50 the set point will be that set Coo Hea With input at 100 the current set point will be adjusted set Coo Hea b15 2 NOTE In cooling mode consideri...

Страница 13: ...val of time P16 the circulator is turned on for a time equal to P17 seconds The function is disabled with P17 0 default The periodic function is suspended in the case of antifreeze mode intervention 8...

Страница 14: ...during this function the flow switch alarm is disabled the maintenance technician must guarantee that there is water inside the system 9 COMPRESSOR ON OFF LOGIC The restart of compressors is in operat...

Страница 15: ...see Chapter 5 and the relative control must also be enabled with parameter H85 6 default The domestic hot water DHW function is controlled through parameter H10 Parameter VALUE Function H19 6 DHW temp...

Страница 16: ...ctrical bridge must be removed from the terminal block With the contact open the unit will be in stand by mode in this state the message E00 will appear on the display on the machine When the contact...

Страница 17: ...2 0 Function not active 1 Enable Hz minimum L03 0 Function not active 1 Function active only in cooling mode 2 Function active only in heating mode 3 Function active only in sanitary mode 4 Function a...

Страница 18: ...ed mode With the function active the noise output and power of the unit are limited for additional information see the installer user manual 20 PARTIAL RECOVERY WITH DESUPERHEATER IF DS ACCESSORY IS P...

Страница 19: ...o lockout due to the intervention of an alarm It switches off when the machine finishes DHW production also taking into account any offset on the set point set with parameter r31 Parameter VALUE Funct...

Страница 20: ...f boiler use r32 1 3 Boiler equipment 21 7 LOGIC OF INTEGRATION HEATERS AND OR BOILER IN JOINT OPERATION OR IN SUB STITUTION OF THE HEAT PUMP COMPRESSOR The auxiliary parts that can be used for joint...

Страница 21: ...o thermoregulated by the system water remote probe as described above If the remote system water probe is not active the boiler is controlled by the flow probe of the heat pump 21 8 3 OPERATION IN SUB...

Страница 22: ...r12 minutes plant inte gration heater HEAT HEAT SAN HEAT 1 0 1 2 Set the minutes 4 6 1 3 1 Heat pump 2 After r16 minutes DHW integration heater HEAT SAN SANITARY 0 1 1 Set the minutes 0 1 4 2 3 1 Hea...

Страница 23: ...s 6 3 1 Plant DHW integration heater 2 After r12 minutes heat pump HEAT HEAT SAN HEAT SANITARY 1 1 Set the minutes Set the minutes 0 3 TABLE 4 OPERATION IN SUBSTITUTION INTERVENTION ORDER STATUS OPERA...

Страница 24: ...unt are interrupted With remote on off contact open the Plant inte gration heater is deactivated Works as indicated in TABLES 1 2 3 and 4 COOL SAN DHW Cannot be actived Works as indicated in TABLE 5 C...

Страница 25: ...I 0 Digital inputs N A 1 Polarit invertita di ID9 H77 Digital inputs polarity 0 0 255 I 0 Digital inputs N A 1 ID7E1 polarity inverted 2 ID8E1 polarity inverted 4 ID9E1 polarity inverted 8 ID10E1 pola...

Страница 26: ...ter is present Contat company r03 Antifreeze heaters setpoint in cooling mode C 4 3 6 I Only change if gly col water is present Contact company r06 Antifreeze heaters delta C 2 0 0 0 25 5 I Only chang...

Страница 27: ...a period of 10 seconds from the start of the machine after the bypass time the status of the digital input is considered if it is active the presence of flow is considered If a lack of flow is diagno...

Страница 28: ...ber of alarm interventions in one hour is 3 the alarm becomes manual reset 24 12 E041 4 WAY VALVE This alarm identifies a malfunction of the 4 way valve for reversing and is manual reset The alarm is...

Страница 29: ...g to your requirements you must modify the following parameters Parameter VALUE Function H124 0 Baud rate 4800 bit s 1 Baud rate 9600 bit s 2 Baud rate 19200 bit s 3 Baud rate 38400 bit s H125 0 Parit...

Страница 30: ...nlet 401 C 10 R Water outlet 405 C 10 R ACS If active 428 C 10 R External 433 C 10 R Compressor 1 discharge 440 C 10 R Remote system If active 7000 10 R Analogue output Condensaton fan 7001 10 R Circu...

Страница 31: ...module Gi Probe 11 If active 954 BOOL 1 R ALARM E801 Inverter link 1 2 ALARM E802 Inverter link 2 4 ALARM E851 Hardware fault inverter 1 5 ALARM E852 Hardware fault inverter 2 7 ALARM E861 Overcurrent...

Страница 32: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 32...

Страница 33: ...33 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...

Страница 34: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 34...

Страница 35: ...35 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...

Страница 36: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Отзывы: