3.

 

enter “

Clock

”; 

4.

 

set date and time using the arrows (the values to adjust will be red-coloured); 

5.

 

when all values are set, press the icon with the tick to confirm. 

 

Figure 32. "Clock" page. 

4.8

 

DIAGNOSTIC ERRORS 

4.8.1

 

ACTIVE ALARMS 

You can view the current alarms of the connected units. To do this, from the home page, press the danger triangle icon, if present; 

from here you can access the list of all active alarms in the system.  

Also, when a unit is displayed (i.e. Chiller page, see Paragraph 3.4.1), by pressing the triangle that appears on the machine, you go to 

a menu where you can see the current alarms of the selected machine.  

4.8.2

 

ALARM HISTORY  

The keyboard manages a detected alarms list for all the plant that shows the date and time of the alarm, the affected machine and 

alarm type. The alarm history stores up to 100 alarms; once this limit is exceeded, it automatically deletes the older alarms. 

To go to the alarm history: from the system main page, go into "

Configuration

" -> "

Service menu

" -> "

Alarm log

". 

Having the service password, you can set that the alarm history is also accessible from the user menu; to do  this go into 

"

Configuration

" -> "

Service menu

" -> "

Parameters

" -> 

"Keyboard"

 -> 

Par 33/65: Enable user alarm log = 1.

 

4.9

 

DOUBLE SET-POINT FUNCTIONS 

The double set-point function introduces a second plant side set-point (both in cooling mode and in heating mode). 

The application field is primarily that of the floor-cooling assisted by fan coil units for dehumidification. 

The purpose of the application is to prevent the formation of condensation on the floor in any condition, and in any case to ensure 

thermo hygrometric well-being. 
The double set-point is activated from service parameter (from System main page -> 

Configuration

 ->

 Service menu

 -> 

Parameters

 -> 

Chiller

 -> 

Chiller name

 -> 

H129: Enable second setpoint ≥ 2

, ref. the control manuals of the chiller unit for allowable values). It is also 

required to set a digital output for controlling the three-way valve used to divert the flow of water between the floor and fan coils. 

The humidistat function is instead carried out directly by the Hi-T2 remote control panel, by means of its integrated probes and the 

logic internally implemented related to the control of dew point and dehumidification. 

Please refer to the manual of the chiller for the correct setting of parameters related to the double set-point, as well as for the 

electrical connections to be done in the terminal board of the chiller. 
The set-points that can be set with double set-point function enabled are: 

Setpoint  

Setpoint at Hi-T2 

Setpoint onboard control panel 

First setpoint (°C) 

T water 

Coo/Hea 

First setpoint eco (°C) 

T Water ECO 

  

Second setpoint (°C) 

T2 water 

Co2/He2 

Second setpoint eco (°C) 

T2 water ECO 

  

Table 4. Set point settings with double set point enabled. 

To manage the setpoint: 

 

from the Hi-

T2 controller →

“Set-point setup”

 menu -> 

“Chiller” 

->

”Summer” 

or 

“Winter”

 (see Paragraph 4.6.3). 

 

from the on-

board control panel → SET button.

 

The second setpoint is higher than the first set point in summer and lower in winter: 

 

in summer: T

2

 

≥ T

 

 

in winter: T

2

 

≤ T

 

Содержание Hi-T2

Страница 1: ......

Страница 2: ...REMOTE CONTROL FOR CHILLERS AND HYDRONIC TERMINALS Any waste electrical and electronic products must not be disposed of with normal household waste but disposed of in accordance with the WEEE law base...

Страница 3: ...3 6 3 PROGRAMS PAGE CHRONOTHERMOSTAT 16 3 6 4 SPECIAL FUNCTIONS PAGE 17 3 6 5 CONFIGURATION PAGE 17 3 6 6 HELP PAGE 19 4 MACHINES STATUS AND FUNCTIONS 19 4 1 NETWORK MANAGEMENT 19 4 2 CHILLER HEAT PU...

Страница 4: ...IONS 33 4 12 SPECIAL FUNCTIONS 33 4 12 1 SCREED FUNCTION 33 4 13 PASSWORD AND PROTECTIONS 34 5 REMOTE ACCESS 34 5 1 SECURITY 34 5 2 LOCAL WEB SERVER 34 6 FIRMWARE UPDATE 37 7 HI T2 CONFIGURATION PARAM...

Страница 5: ...ls and heat pumps For multi circuit units only the resources and parameters of the first circuit are displayed 1 2 PROHIBITED USE Any use different than that permitted is PROHIBITED 1 3 TECHNICAL DATA...

Страница 6: ...touch screen in contact with other electrical devices Electrostatic discharge may cause a malfunction 2 1 3 DISPLAY The display is a TFT LCD 16 9 format with a diagonal 4 3 The resolution is 480 x 27...

Страница 7: ...holes which can be removed by exerting the required force with a manual screwdriver in order to get fixing holes Of the 6 slots use only the outer 2 slots of the horizontal series see figure Before ca...

Страница 8: ...ng example The colour saturation indicates that the icon is usable when pressed the related function is performed The transparency indicates that the icon is not usable and touching it has no resultin...

Страница 9: ...rsion 7 Configuring the Ethernet network 8 Log out intermittent symbol if active 9 Navigation arrow next page Graphically it also contains information on the presence or absence of the following utili...

Страница 10: ...coils if the fan coil symbol appears Figure 8 Networked fan coils Fan coil units in dehumidification mode if the symbol of the drops on the fan coil appears Figure 9 Fan coils in dehumidification mode...

Страница 11: ...hold the sensitive area 4 indicated in Figure Once you find the chiller press and hold for a few seconds in the same area 4 Compose the desired name with the display keyboard Figure 11 Insert chiller...

Страница 12: ...TER 2 DHW INTEGRATION HEATER 3 PLANT INTEGRATION HEATER 4 BOILER ENABLING 5 DOUBLE SET POINT 6 DEHUMIDIFYING 7 SCREED FUNCTION 8 DEFROST 9 ANTIFREEZE WATER 10 ANTIFREEZE TRAY HEATER Table 1 Order of a...

Страница 13: ...the name area you go to the next fan coil unit in the network 3 4 and 5 Navigation bar The information on the fan coil page is given below 6 Detected temperature in the fan coil zones the average valu...

Страница 14: ...1 WINDOW CONTACT 2 DOUBLE SET POINT 3 HUMIDITY CONTROL Table 2 Order of appearance of the icons in the fan coils function bar 3 4 3 AREA Hi T2 Pressing on the sensitive area 6 of Figure 5 you have ac...

Страница 15: ...and the relative humidity measured by the probes integrated in the Hi T2 panel Field 5 indicates the presence of the solar panel system then the indication on the temperature of the solar panels is s...

Страница 16: ...ndividual units 3 6 2 SET POINT SETUP PAGE Press the button to enter the Set point setup page Figure 18 Set point setup page From this screen you can set the parameters of the chiller and of the confi...

Страница 17: ...the User Keyboard setup menu the Service menu and the Manufacturer menu Pressing each of these items a numeric keypad will appear for entering a password Figure 21 Password entry The user password is...

Страница 18: ...ress outside the confirmation area it will go back to the previous value 3 6 5 2 SERVICE MENU In order to access the menu you must set the service password From here you can configure the network by p...

Страница 19: ...control as shown in the drawing In the Hi T2 remote control by setting the parameter Par 8 65 Configuration Service Menu Keyboard related to the number of chillers in the network you can configure th...

Страница 20: ...The set point will be sent also to the fan coils of the zone they belong to Note that a correction can be made locally by means of the fan coil s knob 4 4 INITIAL CONFIGURATION PROCEDURE OF Hi T2 REMO...

Страница 21: ...ess Enter otherwise press Esc 5 press on the value that appears near the wording From the value is highlighted in red 6 use the arrows keys to select the address of the first fan coil of the zone that...

Страница 22: ...Status setup screen the following icons may appear near the units zones set OFF MANUAL MANUAL ECO PROGRAMMED ROOM THERMOSTAT Another way to set only certain zones units in a given status can be as fo...

Страница 23: ...this case both Manual and Manual eco set the chillers in DHW manual mode Note once the DHW status is set from the Hi T2 control panel you must wait about a minute to ensure that communication with th...

Страница 24: ...within the indicated maximum and minimum limits and then confirm Water setting Eco water setting DHW setting DHW Preparator setting Zone 1 WINTER SUMMER Set Eco setting Change the set value using the...

Страница 25: ...mal operation use of normal water control settings Economical operation use of the economic water regulation settings The weekly programming in summer operation is distinct from that in winter mode Fi...

Страница 26: ...ngs are Zone off Zone in normal operation normal ambient setpoint Zone in economical operation eco ambient setpoint Then entering Summer Zones or Winter Zones a list of all set zones will appear At th...

Страница 27: ...he pink line shows any setting of the previous day that overruns into the present day because the duration exceeds midnight It is necessary to enable the electric heaters in DHW integration by setting...

Страница 28: ...e Hi T2 thermostat is greater than the zone setpoint and the heat pump is in standby mode Figure 30 Second Main page On the individual fan coil screen the displayed temperature is the one given by the...

Страница 29: ...cooling assisted by fan coil units for dehumidification The purpose of the application is to prevent the formation of condensation on the floor in any condition and in any case to ensure thermo hygro...

Страница 30: ...UMIDIFICATION ICON if dehumidification is active Table 6 Double set point dehumidification icons 4 9 1 DEW POINT CONTROL The dew point temperature will be calculated by reading the internal temperatur...

Страница 31: ...ler in cooling 0 50 C 12 65 Set Text comp CHIL Heat Setpoint of external temp For climatic compensation of the chiller in heating 20 35 C 13 65 m1 comp Text CHIL Angular coefficient of the chiller com...

Страница 32: ...ients for heating Offset describes the expected maximum variation of the water setpoint It can be set from 0 to 3 Figura 34 Chiller s climatic compensation In order to exclude the climatic compensatio...

Страница 33: ...ion changes by the user the offsets must be set to be zero from the Settings Zone menu To exclude the climatic compensation changes by the maintenance technician the coefficients m must be set to be z...

Страница 34: ...vity or after 20 minutes from accessing the current level of protection These timing values can be modified from service or manufacturer parameter There is a password to unlock the screensaver set by...

Страница 35: ...ating command allows you to choose between OFF programmed mode manual mode manual economy mode The following statuses can be set for the season change summer summer sanitary winter winter sanitary onl...

Страница 36: ...he setpoints set for the summer season appear under Summer Water setpoint Economy water setpoint and if the double setpoint is enabled Second water setpoint and Second economy water setpoint Figure 41...

Страница 37: ...illers are those shown in the user installer manual of I 32V5 chiller heat pump units The service parameters of the keyboard are shown in the following table N PARAMETER NAME MINIMUM VALUE MAXIMUM VAL...

Страница 38: ...0 Flag 46 Regulation temperature in zone 1 winter 0 Average temp of the fan coils of the zone 1 Minimum temp of the fan coils of the zone 2 Maximum temp of the fan coils of the zone 3 Temperature mea...

Страница 39: ...temp of the fan coils of the zone 2 Maximum temp of the fan coils of the zone 3 Temperature measured by Hi T2 0 3 3 56 Regulation temperature in zone 2 summer 0 Average temp of the fan coils of the zo...

Страница 40: ...n zone 8 summer 0 Average temp of the fan coils of the zone 1 Minimum temp of the fan coils of the zone 2 Maximum temp of the fan coils of the zone 3 Temperature measured by Hi T2 0 3 1 63 Regulation...

Страница 41: ...ral band 0 Neutral band 4 0 C 1 Neutral band 3 0 C 2 Neutral band 2 0 C 3 Neutral band 1 0 C 4 Neutral band 0 C 0 4 2 3 Plant type 0 2 PIPE plant 1 4 PIPE plant 0 1 0 4 Fan mode 0 CONTINUOUS FAN 1 FAN...

Страница 42: ...arrow keys to scroll through the pages of the parameters up to the desired parameter press on the currently set value the current value turns red to indicate that it can be changed by using the up and...

Страница 43: ...em It is also possible to connect in cascade chillers heat pumps of different output capacities the Hi T remote control panel can determine the installed output From the remote control display you can...

Страница 44: ...Hi T2 Centralised controller 44...

Страница 45: ......

Страница 46: ...Advantix SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Отзывы: