i-SHWAK V4
Inverter air/water chillers and heat pumps with wall-mounted indoor unit and remote condensing outdoor unit
33
15
ELECTRIC DATA
Power supply of the unit
V/~/Hz
230/1/50*-400/3/50**
Power supply of circulator and
diverting valve (optional kit VDIS1)
Indoor unit
V/~/Hz
230/1/50
Outdoor unit control board circuit
V/~/Hz
12/1/50
Outoor fans power supply
V/~/Hz
230/1/50
Indoor unit control board circuit
V/~/Hz
12/1/50
Electric heraters power supply
V/~/Hz
See the power
supply of the unit
* For single-phase indoor units and for outdoor units of i-SHWAK V4 06, 08, 10, 12, 14 and 16 models.
** For three-phase indoor units and for outdoor unit of i-SHWAK 14T e 16T models.
Note: Electric data may change for updating the manual. It is therefore necessary to refer always to the technical data label
sticked on the right-side panel of the unit.
15.1 INDOOR UNIT MAXIMUM POWER CONSUMPTION/MAXIMUM INPUT CURRENT
E-heater
Model
Not present
1,2 kW
2 kW
3 kW
4,5 kW
Powe supply
MP1 06 / 08
0,08 kW / 0,62 A
1,34 kW / 6,10 A
2,08 kW / 9,31 A
3,08 kW / 13,66 A
4,58 kW / 20,18 A
230V/1/50Hz
MP3 06 /08
0,08 kW / 0,62 A
ND
2,08 kW / 3,51 A
3,08 kW / 4,95 A
4,58 kW / 7,12 A
400V/3P+N+T/50Hz
MP1 10 / 12
0,10 kW / 0,72 A
1,36 kW / 6,20 A
2,10 kW / 9,41 A
3,10 kW / 13,76 A
4,6 kW / 20,28 A
230V/1/50Hz
MP3 10 / 12
0,10 kW / 0,72 A
ND
2,10 kW / 3,61 A
3,10 kW / 5,05 A
4,6 kW / 7,22 A
400V/3P+N+T/50Hz
MP1 14 / 16
0,15 kW / 1,07 A
1,41 kW / 6,55 A
2,15 kW / 9,76 A
3,15 kW / 14,11 A
4,65 kW / 20,63 A
230V/1/50Hz
MP3 14 / 16
0,15 kW / 1,07 A
ND
2,15 kW / 3,96 A
3,15 kW / 5,40 A
4,65 kW / 7,57 A
400V/3P+N+T/50Hz
MPR1 06 / 08
0,13 kW / 1,06 A
1,39 kW / 6,54 A
2,13 kW / 9,75 A
3,13 kW / 14,10 A
4,63 kW / 20,62 A
230V/1/50Hz
MPR3 06 / 08
0,13 kW / 1,06 A
ND
2,13 kW / 3,95 A
3,13 kW / 5,39 A
4,63 kW / 7,56 A
400V/3P+N+T/50Hz
MPR1 10 / 12
0,14 kW / 1,16 A
1,40 kW / 6,64 A
2,14 kW / 9,85 A
3,14 kW / 14,20 A
4,64 kW / 20,72 A
230V/1/50Hz
MPR3 10 / 12
0,14 kW / 1,16 A
ND
2,14 kW / 4,05 A
3,14 kW / 5,49 A
4,64 kW / 7,66 A
400V/3P+N+T/50Hz
MPR1 14 / 16
0,19 kW / 1,51 A
1,45 kW / 6,99 A
2,19 kW / 10,20 A
3,19 kW / 14,55 A
4,69 kW / 21,07 A
230V/1/50Hz
MPR3 14 / 16
0,19 kW / 1,51 A
ND
2,19 kW / 4,40 A
3,19 kW / 5,84 A
4,69 kW / 8,01 A
400V/3P+N+T/50Hz
The electrical data of the outdoor and indoor units are set to scale the size of the circuit breakers and power supply cables. You have to add the input power of
the outdoor unit (see Paragraph 14.2) and indoor unit depending on the installed electric heater kit.
16
HYDRAULIC CIRCUIT’S
AVAILABLE HEAD PRESSURES
The characteristic curves corresponding to prevalence-water flow rate without head losses of the hydronic kit, which is composed
of the components described in Paragraph 6.10 are shown below. The optimal operating points of the different models are shown
on the following curve according to the conditions indicated in the apex 3 of the paragraph 14.3. The curves are reported without
considering the contribution due to the load losses of the three-way valve (only if the optional VDIS1 kit is present). The plant
must be designed so as to ensure the nominal water flow rate corresponding to the operating points indicated below.