5 Sequence Function
63
DOEF series
Matsusada Precision
5 Sequence Function
5-1 Overview
The unit is equipped a sequence function, which enables it to generate various types of outputs with
pre-set programs.
A
“step” is a unit waveform set for a certain amount of time, so-called “step time” and more than one step
forms a single program.
A program is configured with more than one step to form a waveform pattern.
The sequence function is possible to set output waveforms with 1,024 steps in CV mode and CC mode
respectively. As the number of programs is also freely set to one to 64 in CV mode and CC mode
respectively, it allows the unit to execute multiple programs linked.
For example, when program 1 with 64 steps is finished, execute program 10 with 10 steps, and when the
program 10 is finished, and then.... Such kind of operation is possible.
As all setting data for step and program are stored in memory, they will remain even if the power of the unit
is turned off.
Moreover, a large amount of data in CV mode and CC mode with 1,024 steps respectively as well as the
number of programs and steps are possible to be stored, which has improved easy to use.
Step N
Program 10
Step 7
Step N
Program 1
Step 1
Step 2
Step 3
Program 25
Program 4
A step determines an
output waveform for a
certain
amount
of
time
Linking programs to execute.
Содержание DOEF Series
Страница 1: ...Instruction Manual F RA 001 3R2 MODEL DOEF series B N 243 9 024 243 9 024 Rev 0 4 ...
Страница 15: ...2 External Appearance 7 DOEF series Matsusada Precision 2 3 Dimensions 2 3 1 400W Model ...
Страница 16: ...2 External Appearance 8 DOEF series Matsusada Precision 2 3 2 600W Model ...
Страница 17: ...2 External Appearance 9 DOEF series Matsusada Precision 2 3 3 1200W Model ...
Страница 121: ......
Страница 123: ......
Страница 124: ......