background image

5

The basic logic on which a High or Low Level Alarm is determined, is set out in the Table below:

If there is a Low Level Alarm, then both Pumps will be locked out until the alarm is manually reset. This lockout will only be 

over ridden upon a High Level condition where both the Pump Start and High level inputs are closed.

Note that after a High level is triggered, the pumps will both run until the Pump Start and Stop inputs are opened.

Mode C: Standard Configuration plus Prime Loss

As per Mode A, except Input 1 is connected to a prime loss/flow switch. If at any stage, after Pump Start, or whilst a pump 

is running, the Prime Loss input opens, for a continuous 1 minute period, a fault is immediately triggered for that pump 

and duty alternates. Input functions are as follows:

Mode D: Pressure Pumping Configuration

Duty Pump:  

Lead Pump

Standby Pump: 

Lag Pump

Input functions are as follows:

Typical Operation for Mode D:

• 

Pressure drops to 400kPa: Lead (for this cycle) Pump cuts in.

• 

Pressure increases and Pump cuts out.

• 

Cycle continues with duty (Lead and Lag) alternating between the two pumps.

• 

If pressure drops to 350kPa, Lead Pumps will cut in and remain running until Lead Pressure Switch opens circuit. 
Then duty alternates.

• 

No faults are logged against the Lead Pump if the Lag Pump starts.

• 

The controller has inbuilt timers for “Delayed” Start and Stop to obviate pump chatter. Upon Input 1 contact closure, 
the pump will not start (delay start) for 1 second and will not stop (minimum run time) for 10 seconds (or 11 sec-
onds from close of Input contacts). This “run on” occurs even if Lead Pressure switch opens circuit during this initial 
period. If however run time exceeds 11 seconds, the pump will stop immediately upon “Open Circuit” occurring.

• 

If the Lead Pressure Switch input closes circuit as well as he Low Pressure Switch input, both pumps will be turned 
on and the Low Pressure Timer will begin counting. If this condition exists for a period of 60 seconds, then both 
pumps are shut down and the system signals a level alarm. This would be typical of a Loss of Prime, or Burst main 
situation.

• 

Pressure switches are normally Closed and Opened on High Pressure.

Input 2

Pump Stop

Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed

Input 1

Low Level

Closed
Closed
Closed
Closed

Open
Open
Open
Open

Input 3

Pump Start

Open

Closed
Closed

Open
Open

Closed

Open

Closed

Input 4

High Level

Open
Open

Closed
Closed

Open
Open

Closed
Closed

Pump

State

Off
On

Both On
Both On

Off
Off
Off

Both On

Alarm

-
-

High Level (after Timeout)
High Level (after Timeout)

-

Low Level
Low Level

High Level (after Timeout)

Input         Function

Input 1      Prime Loss

Input 2      Pump Stop

Input 3      Pump Start

Input 4      High Level

Input         Function

Input 1      Not Used

Input 2      Lead Pump Pressure Switch (set at say 350kPa)

Input 3      Lag Pump Pressure Switch (set at say 350kPa)

Input 4      Low Pressure Switch (set at say 200kPa)

Содержание FPC-30000

Страница 1: ...U A L P U M P C O N T R O L L E R AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON Steady Overload Flash Prime Loss Steady Overload Flash Prime Loss Press and hol...

Страница 2: ...WARNING All electrical connections must be carried out by a suitably qualified and registered electrician Prior to Installation ensure power supply is isolated Power supply must be Circuit Breaker Pr...

Страница 3: ...EL F SET THERMAL OVERLOADS TO SUIT PUMP 1 Controller enclosure must be mounted in a vertical position 2 Ensure mounting method does not compromise enclosure weather proof rating 3 Ensure access to mai...

Страница 4: ...vel input must be closed for Pump Start and Pump Stop inputs to function The High Level input however will still override the Low Level and run both pumps Input functions are as follows Position Off O...

Страница 5: ...to obviate pump chatter Upon Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 sec onds from close of Input contacts This...

Страница 6: ...Alarm Delay Typically used for Storm Water applications High Level Alarm delay in this mode is 15 minutes Setting this DIP Switch to On will cause the High level Alarm to remain active until the contr...

Страница 7: ...TPUT 10amp CONTROL CIRCUIT BREAKER ISOLATOR SWITCH STROBE BUZZER TRANSFORMER 12Vac 240Vac INPUT 1 SWITCH INPUT 2 SWITCH INPUT 3 SWITCH INPUT 4 SWITCH 12Vdc 12Vdc P U M P 1 P U M P 2 D U A L P U M P C...

Страница 8: ...C O N T R O L L E R AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON Steady Overload Flash Prime Loss Steady Overload Flash Prime Loss Press and hold for 3 secs to...

Отзывы: