This controller can perform control functions for most Dual Pump  pumping applications. It is more than likely that the con-

trol parameters have already been set up for your particular application, however, hereunder you will find details of the set 

up and configuration options.

There are 6 DIP switches located on the lower side of the control module, which allows for selecting “mode” and “feature” 

options, as per the following table:

Mode A: Standard Configuration

Start/Stop/High Level operation. When the Pump Start input is closed contact (triggered), the Duty Pump will be turned on. 

The pump will remain on until both the Pump Start and Pump Stop Inputs have turned off (Open Circuited). Upon High Level, 

both pumps will run until the Pump Stop Input turns off.

In addition to this, there is a maximum idle timer, which will trigger a Pump Start condition, if either pump has not run for 4 

hours, and the Stop Float Contacts are closed. The pump will continue to run until the Stop Float Contacts open. Input func-

tions are as follows:

Mode B: Standard Configuration plus Low Level Alarm

As per Mode A, except it has an active Low Level input. The Low Level input must be closed, for Pump Start and Pump Stop 

inputs to function. The High Level input however, will still override the Low Level and run both pumps. Input functions are as 

follows:

 

      

Position

Off/Off

Off/On

On/Off

On/On

Off

On

Off

On

Off

On

Off

On

Function

Mode A:

 Standard typical float switch configuration (Start, Stop and High Level). No Low Level

Mode B:

 Standard configuration plus low level (Start, Stop, High Level and Low Level).

Mode C:

 Standard configuration plus Prime Loss enabled, on Low Level (Input 1)

Mode D:

 Pressure Pumping configuration (Lead, Lag and Low Pressure)

Operating Pump alternates each time a pump start is triggered, or after 30 minutes continuous 

running.

Operating Pump alternates after 6 hours continuous running.

Anti-seize Timer disabled

Anti-seize Timer 6 seconds every 7 days enabled

When placed in Manual Mode, pump remains in Manual Mode

When placed in Manual Mode after 5 minutes the pump will revert to Auto

High Level Alarm automatically resets upon open circuit of high level input. High Level alarm 

has 15 minute delay.

High Level Alarm can only be reset manually. High Level Alarm has 5 minute delay. 

DIP Switch

1/2

3

4

5

6

Input        Function

Input 1     Not used

Input 2     Pump Stop

Input 3     Pump Start

Input 4     High Level

Input         Function

Input 1      Low Level

Input 2      Pump Stop

Input 3      Pump Start

Input 4      High Level

OPERATION

Содержание FPC-30000

Страница 1: ...U A L P U M P C O N T R O L L E R AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON Steady Overload Flash Prime Loss Steady Overload Flash Prime Loss Press and hol...

Страница 2: ...WARNING All electrical connections must be carried out by a suitably qualified and registered electrician Prior to Installation ensure power supply is isolated Power supply must be Circuit Breaker Pr...

Страница 3: ...EL F SET THERMAL OVERLOADS TO SUIT PUMP 1 Controller enclosure must be mounted in a vertical position 2 Ensure mounting method does not compromise enclosure weather proof rating 3 Ensure access to mai...

Страница 4: ...vel input must be closed for Pump Start and Pump Stop inputs to function The High Level input however will still override the Low Level and run both pumps Input functions are as follows Position Off O...

Страница 5: ...to obviate pump chatter Upon Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 sec onds from close of Input contacts This...

Страница 6: ...Alarm Delay Typically used for Storm Water applications High Level Alarm delay in this mode is 15 minutes Setting this DIP Switch to On will cause the High level Alarm to remain active until the contr...

Страница 7: ...TPUT 10amp CONTROL CIRCUIT BREAKER ISOLATOR SWITCH STROBE BUZZER TRANSFORMER 12Vac 240Vac INPUT 1 SWITCH INPUT 2 SWITCH INPUT 3 SWITCH INPUT 4 SWITCH 12Vdc 12Vdc P U M P 1 P U M P 2 D U A L P U M P C...

Страница 8: ...C O N T R O L L E R AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON Steady Overload Flash Prime Loss Steady Overload Flash Prime Loss Press and hold for 3 secs to...

Отзывы: