DOC:  DPC 30000 & 30005
REVISED:  220410

HIGH

LEVEL

ON STEADY

High Level Fault has occurred during three successive pump runs

SLOW FLASH

Overload/Thermostat Fault has occurred during three successive pump runs

FAST FLASH

Maximum run time has been exceeded during three successive pump runs

ON STEADY

Pump switched on but not running

FLASHING

Pump switched on and running

HIGH LEVEL ON

A high level has been present for more than 3 minutes

RUNNING

FAULT

PUMP 1

PUMP 2

FOR SINGLE FLOAT SWITCH APPLICATIONS, CONNECT CLOSE ON RISE FLOAT SWITCH TO ‘START’ CONTACTS

EARTH

EARTH

EARTH

A

CTIVE

NEUTR

AL

A

CTIVE

NEUTR

AL

PUMP 1

PUMP 2

SUPPLY 240Vac

A

CTIVE

NEUTR

AL

240Vac

SUPPLY

WARNING: HIGH VOLTAGE

WIRING CONNECTION DETAIL

FPC-30000 & FPC-30005

INDICATOR LIGHTS GUIDE

ALL ELECTRICAL CONNECTIONS MUST BE CARRIED OUT

BY A SUITABLY QUALIFIED ELECTRCIAN

ACCESS BY AUTHORISED PERSONNEL ONLY

HIGH

LEVEL

ON STEADY

High Level Fault has occurred during three successive pump runs

SLOW FLASH

Overload/Thermostat Fault has occurred during three successive pump runs

FAST FLASH

Maximum run time has been exceeded during three successive pump runs

ON STEADY

Pump switched on but not running

FLASHING

Pump switched on and running

HIGH LEVEL ON

A high level has been present for more than 3 minutes

RUNNING

FAULT

FOR SINGLE FLOAT SWITCH APPLICATIONS, CONNECT CLOSE ON RISE FLOAT SWITCH TO ‘START’ CONTACTS

WARNING: HIGH VOLTAGE

WIRING CONNECTION DETAIL

FPC-30000 & FPC-30005

INDICATOR LIGHTS GUIDE

ALL ELECTRICAL CONNECTIONS MUST BE CARRIED OUT

BY A SUITABLY QUALIFIED ELECTRCIAN

ACCESS BY AUTHORISED PERSONNEL ONLY

START/MEDUIM

LEVEL

FLOAT SWITCH

HIGH ALARM

LEVEL

FLOAT SWITCH

COMMONCOMMON

N/O CL

OSE ON RISE

COMMON

N/O CL

OSE ON RISE

INPUT 3

START

LEVEL

INPUT 4

HIGH

LEVEL

FLOAT SWITCH CONNECTIONS

12Vdc CONNECTIONS

BLUE NOT REQUIRED

PUMP 1

PUMP 2

EARTH

A

CTIVE

NEUTR

AL

A

CTIVE

NEUTR

AL

PUMP 1

PUMP 2

SUPPLY 240Vac

A

CTIVE

NEUTR

AL

240Vac

SUPPLY

STOP/LOW

LEVEL

FLOAT SWITCH

START/MEDUIM

LEVEL

FLOAT SWITCH

HIGH ALARM

LEVEL

FLOAT SWITCH

COMMON

N/O CL

OSE ON RISE

LOW ALARM

 REDUNTANT STOP

FLOAT SWITCH

COMMON

N/O CL

OSE ON RISE

COMMONCOMMON

N/O CL

OSE ON RISE

COMMON

N/O CL

OSE ON RISE

INPUT 2

STOP

LEVEL

INPUT 3

START

LEVEL

INPUT 4

HIGH

LEVEL

AUX

CODED

DATA

OUTPUT

BMS

INPUT 1

LOW

LEVEL

FLOAT SWITCH CONNECTIONS

12Vdc CONNECTIONS

BLUE NOT REQUIRED

SET THERMAL OVERLOADS TO SUIT PUMP

1.  Controller enclosure must be 
     mounted in a vertical position.
2.  Ensure mounting method 
     does not compromise enclosure 
     weather proof rating.
3.  Ensure access to main isolator 
     is not restricted.
4.  Ensure cables/conduits 
     entering the panel have 
     mechanical protection and that 
     the penetrations are 
     sealed and do not compromise 
     the weather proof rating of the 
     enclosure.

MOUNTING

FRONT VIEW

Top

Bottom

Top

Bottom

Mounting 

Frame/

Wall

CONNECTION

OFF

  ON 

P U M P   1

P U M P   2

D U A L   P U M P   C O N T R O L L E R

AUTO

OFF

AUTO

OFF

MAN

MAN

MUTE/

RESET

PUMP ON

PUMP ON
FAULT

FAULT

LEVEL

ALARM

POWER

ON

Steady - Overload

Flash - Prime Loss

Steady - Overload

Flash - Prime Loss

Press and hold

for 3 secs to reset 

Steady - High Level

Flash - Low Level

INSTALLATION

SIDE VIEW

3

NOTE:

 

Controller must be earthed and all electrical connections must be carried out by a suitably qualified 

           Electrician. For Single Working Level Float Switch Applications, connect to “Start (Input 3)” terminals  
           only, and NO bridge wire is required in “Stop (Input 2)” terminals.

Содержание FPC-30000

Страница 1: ...U A L P U M P C O N T R O L L E R AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON Steady Overload Flash Prime Loss Steady Overload Flash Prime Loss Press and hol...

Страница 2: ...WARNING All electrical connections must be carried out by a suitably qualified and registered electrician Prior to Installation ensure power supply is isolated Power supply must be Circuit Breaker Pr...

Страница 3: ...EL F SET THERMAL OVERLOADS TO SUIT PUMP 1 Controller enclosure must be mounted in a vertical position 2 Ensure mounting method does not compromise enclosure weather proof rating 3 Ensure access to mai...

Страница 4: ...vel input must be closed for Pump Start and Pump Stop inputs to function The High Level input however will still override the Low Level and run both pumps Input functions are as follows Position Off O...

Страница 5: ...to obviate pump chatter Upon Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 sec onds from close of Input contacts This...

Страница 6: ...Alarm Delay Typically used for Storm Water applications High Level Alarm delay in this mode is 15 minutes Setting this DIP Switch to On will cause the High level Alarm to remain active until the contr...

Страница 7: ...TPUT 10amp CONTROL CIRCUIT BREAKER ISOLATOR SWITCH STROBE BUZZER TRANSFORMER 12Vac 240Vac INPUT 1 SWITCH INPUT 2 SWITCH INPUT 3 SWITCH INPUT 4 SWITCH 12Vdc 12Vdc P U M P 1 P U M P 2 D U A L P U M P C...

Страница 8: ...C O N T R O L L E R AUTO OFF AUTO OFF MAN MAN MUTE RESET PUMP ON PUMP ON FAULT FAULT LEVEL ALARM POWER ON Steady Overload Flash Prime Loss Steady Overload Flash Prime Loss Press and hold for 3 secs to...

Отзывы: