![MasterPower OMEGA 2.2KW LS Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/masterpower/omega-2-2kw-ls/omega-2-2kw-ls_user-manual_1738881009.webp)
7
Below are popular solar panel specifications in the market:
A. 75-A: 75W, Vmp=17.46V, Imp=4.3A, Voc=21.96V
B. 75-B: 75W, Vmp=13.3V, Imp=5.64A, Voc=16.94V
C. 140-A: 140W, Vmp=17.9V, Imp=7.82A, Voc=22.0V
D. 250-A: 250W, Vmp=30.64, Imp=8.16A, Voc=37.38V
Output type
PV Panel 75-A
PV Panel 75-B
PV Panel 140-A
PV Panel 250-A
Three-phase
output
19 pieces in Series
x 2 Strings
(2850W PV Panels)
25 pieces in Series
x 2 Strings
(3750W PV Panels)
19 pieces in Series
(2660W PV Panels)
11 pieces in Series
(2750W PV Panels)
Single-phase
output
19 pieces in Series
x 4 Strings
(5700W PV Panels)
25 pieces in Series
x 3 Strings
(5625W PV Panels)
19 pieces in Series
x 2 Strings
(5320W PV Panels)
11 pieces in Series
x 2 Strings
(5500W PV Panels)
Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors.
2. Check correct polarity of connection cable from PV modules and PV input
connectors. Then, connect positive pole (+) of connection cable to positive
pole (+) of PV input connector. Connect negative pole (-) of connection
cable to negative pole (-) of PV input connector.
3. Make sure the wires are securely connected.
AC Input Connection
CAUTION:
Before connecting to AC power source, please install a separate AC circuit breaker between
inverter and AC utility. It’s recommended to use 25A/2P/230V/4500A circuit breaker.
Recommended terminal types:
CAUTION: Important
Before making AC input connection, be sure to do the following actions to prevent human injury or machine
damage.
1. It’s required to turn off circuit breaker.
2. Make sure to connect single-phase AC input to the L & N input connectors in inverter.