Operating Instructions for Master-Bilt Alarm/Light Module (19-14009) 

1598003200 

 

 

 

19-14009 

Walk-In Temp / Door /Alarm / Light Module 

1. GENERAL WARNINGS 

1.1 

PLEASE READ BEFORE USING THIS MANUAL 

 

  This manual is part of the product and should be kept close to the instrument for easy and quick 

reference. 

  The instrument shall not be used for purposes different from those described hereunder. It cannot be 

used as a safety device. 

  Check the application limits before proceeding. 

 

1.2 

 SAFETY PRECAUTIONS 

 

  Check if the supply voltage is correct before connecting the instrument. 

  Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 

Temperature changes with high atmospheric humidity to prevent the formation of condensation. 

  Warning: disconnect all electrical connections before performing any maintenance operation. 

  Fit the probe where it is not damaged by the end-user. The instrument must not be opened. 

  In case of failure or faulty operation send the instrument back to the distributor (see address) with a 

detailed description of the fault. 

  Consider the maximum current that can be applied to each relay (see Technical Data). 

  Ensure that the wires for probes, loads and the power supply are separated and far enough from each 

other, without crossing or intertwining. 

 

2. GENERAL DESCRIPTION 

Model 

XWA11V, 100x64 mm 

format, is a microprocessor based controller, suitable for temperature 

monitoring in a walk-in cooler or freezer. It is provided with two (2) relay outputs to control lights and 
signal an alarm. It is also provided with one (1) NTC probe input for temperature measurement. One (1) 
output allows the user to program the parameter list with the 

“Hot Key”.

 

 

3. INTERFACE 

 

Содержание 19-14009

Страница 1: ...condensation Warning disconnect all electrical connections before performing any maintenance operation Fit the probe where it is not damaged by the end user The instrument must not be opened In case of failure or faulty operation send the instrument back to the distributor see address with a detailed description of the fault Consider the maximum current that can be applied to each relay see Techni...

Страница 2: ...the light of the cold room KEY COMBINATIONS PRESS SIMULTANEOUSLY To lock and unlock the Keyboard To enter the Programming Mode To exit the Programming Mode HIGH To enter a new value for the HIGH Temp ALARM ALU LOW To enter a new value for the LOW Temp ALARM ALL 3 2 USE OF LEDS Each LED function is described in the following table LED MODE Function ON ALARM signaling ON The light is on C ON Celsius...

Страница 3: ...Press SET up or wait 15s without pressing a key NOTE the set value is stored even when the procedure is exited by waiting the time out to expire 5 2 2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA Each parameter present in the HIDDEN MENU can be removed or put into THE FIRST LEVEL user level by pressing SET down In HIDDEN MENU when a parameter is present in First Le...

Страница 4: ...ents Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each relay and in case of heavier loads use a suitable external relay N B Maximum current allowed for all the loads is 20A 8 1 PROBE CONNECTIONS The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is...

Страница 5: ...CAL DATA Housing self extinguishing ABS Case face 100x64 mm depth 45 5mm Mounting J box or wall mount option Frontal protection IP65 Connections fastons for power 18 fastons for probes and Digital Inputs Power supply 120Vac 10 optional 230Vac 10 Power absorption 4VA max Display 3 digits red LED 14 2 mm high Inputs 1 NTC probe Digital inputs 2 free voltages Relay outputs Dry Contacts Light relay SP...

Страница 6: ...of defrost 30 Pr2 0 255 min dot Delay of Temp alarm after closing the door 15 Pr2 0 255 min LHt Light timer 15 Pr1 0 255 min doA Open door alarm delay 15 Pr1 0 255 min OA1 First relay configuration ALr Pr2 ALr 0 LHt 1 OnF 2 oA2 Second relay configuration LHt Pr2 ALr 0 LHt 1 OnF 2 AOP Alarm relay polarity oP Pr2 OP CL i1P Digital input 1 polarity oP Pr2 OP 0 CL 1 i1L Door switch to turn light ON y ...

Страница 7: ...Open door alarm delay 0 255 min delay between the detection of the open door condition and its alarm signaling the flashing message dA is displayed oA1 First relay configuration 14 15 ALr alarm LHt light onF on off relay oA2 Second relay configuration 14 16 ALr alarm LHt light onF on off relay AOP Alarm relay polarity cL closing contacts oP opening contacts i1P Digital input 1 polarity 1 2 CL the ...