Figure 91 Intrinsically Safe Installation with Galvanic Isolator
CAUTION
Do not connect a HART
®
modem and a PC to a control circuit
unless the controller is HART
®
compatible or has a HART
®
filter.
Loss of control or a process upset can occur if the controller output
circuit is not compatible with HART
®
signals.
NOTE
A control circuit must be HART
®
compatible or have a HART
®
filter
installed. Contact controller or DCS manufacturer. See HART
®
Filter Required for Certain Controls System Output Circuits.
Power
Supply
Hart Compliant
Control System
Output Card
HART
Modem
SVI II ESD
ValVue ESD
I.S. Galvanic
Isolator
Hazardous Area
Non-hazardous Area
HART
Filter
Power
Supply
GE DPI620
Содержание SVI II ESD
Страница 4: ...This page intentionally left blank ...
Страница 10: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 100: ...This page intentionally left blank ...
Страница 120: ...This page intentionally left blank ...
Страница 126: ...This page intentionally left blank ...
Страница 160: ...This page intentionally left blank ...
Страница 194: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 204: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 208: ...This page intentionally left blank ...
Страница 216: ...This page intentionally left blank ...