Model: TC5396
masibus
Doc. Ref. no. : - m105/om/101
Issue no. 00
User’s Manual
Page 17 of 40
6.4 LEVEL 2 TUNE MODE
AUTOTUNE PARAMETERS
Parameter
(PV display)
Setting Name & Description
Default
Value
Show if
Only
Reg.
No.
Symbol
Name
ATUN
(
Atun
)
Auto Tune
Start / Stop Auto Tuning Process
yes
/
no
0 : NO (Stop Auto Tuning)
1 : YES (Start Auto Tuning)
NO
Control
Type(COP) is
PID
6
PB
(
pb
)
Proportional
Band
Adjust Proportional Band
0.1 to 200.0 %
1 0 .0
Control
Type(COP) is
PID
7
TI
(
ti
)
Integral Time
Adjust Integral Time
0 to 1000
6 0
Control
Type(COP) is
PID
8
TD
(
td
)
Derivative
Time
Adjust Derivative Time
0 to 250
0
Control
Type(COP) is
PID
9
CT
(
Ct
)
Cycle Time
Adjust Cycle Time
For, SSR o/p: (1
–
60 sec)
Relay o/p: (10
–
250 sec)
1 0
1 0
O.DIR
(
o.dir
)
Output
Direction
Set Output Direction
dir
/
rev
0 : REV (REVERSE)
1 : DIR (Direct)
0 (R EV)
Control
Type(COP) is
PID
11
MR
(
mr
)
Manual Reset
Adjust Manual Reset Value
It is used to shift P Band for critical Controlling
situations.
-50% to 50% of PB
EX. If PB = 50, SP = 100, O.DIR = REV
MR = 0MR = 25
PV
% POWER
PV
%POWER
<= 75
100 %
<= 100
100 %
100
50 %
125
50 %
>= 125
0 %
>= 150
0 %
-4 0 .0
Control
Type(COP) is
PID
12
ALPH
(
alpH
)
Sampling
Rate
Adjust Sampling Rate
Its acts like Derivative Factor. It is used to
decrease effect of D term in PID output for
some critical operating condition
0.01 to 1.00
1 .0 0
Control
Type(COP) is
PID
13
SMP
(
smp
)
Sampling
Period
Set Sampling Period.
200
/
500
/
1
0 : 200 ms
1 : 500 ms
2 : 1 sec
0
(200 ms)
Control
Type(COP) is
PID
14
RAMP
(
(
Ramp
)
)
Ramp Rate
type
n one
/
min .r
/
hr.r
0:none
1:min.r
2:hr.r
No ne
15
RmpR
(
(
rmpr
)
)
Ramp rate
value
0.1 to 999.9 Degree per minutes or hour
0 .0 0
16
SOKR
(
SOKR
)
Soak rate
0.00 to 99.59 (Format HH.MM )
0.00
17