10.4 Control Output Table for OPEN/OVER/ UNDER Condition
CONTROL OP
Process
Scale
Output
Direction
(O.DIR)
DISPLAY INDICATION
OPEN
OVER
UNDER
RELAY
UP
DIR
ON
ON
OFF
DOWN
REV
OFF
OFF
ON
UP
REV
ON
OFF
ON
DOWN
DIR
OFF
ON
OFF
10.5 Mapping Table for Relay and Retransmission Conditions
Mapping for
Parameters
Mapping
Options
Description
Relay
RL-1
0
(IN 1)
Relay - 1 for Process value 1
1
(IN 2)
Relay - 1 for Process value 2
RL-2
0
(IN 1)
Relay - 2 for Process value 1
1
(IN 2)
Relay - 2 for Process value 2
Retransmission
RT-1
0
(IN 1)
Retransmission - 1 for Process value 1
1
(IN 2)
Retransmission - 1 for Process value 2
RT-2
0
(IN 1)
Retransmission - 2 for Process value 1
1
(IN 2)
Retransmission - 2 for Process value 2
10.6 Jumper Settings for Add-on Card Selection & Retransmission Output
type
There are mainly Two types of Retransmission Output is available:
o
Voltage (0-10VDC, 0-5VDC, 1-5VDC)
o
Current (4-20mADC, 0-20mADC)
This can be Settable by changing the Position of Shorting Link Jumpers on
Retransmission Add-on Card shown in below figure.