Model: LC5296-XP-DC
Doc. Ref. no.:- m61D/om/401
Issue no.: 05
User’s Manual
Page 25 of 31
The error checking field contains a 16-bit value implemented as two eight-bit bytes.
The error check value is the result of a Cyclical Redundancy Check (CRC) calculation
performed on the message contents.
9.2 Modbus Parameter Address
Sr.
No.
Parameters
Absolute
Address
Type
Access Type
1
PROCESS VALUE1
30001
Int
Read Only
2
PROCESS VALUE2
30002
Int
Read Only
3
RELAY-1 STATUS
30006
Int
Read Only
4
RELAY-2 STATUS
30007
Int
Read Only
NOTE:
Process Value (PV) Error Conditions Value
OPEN
:
32767
UNDER
:
32765
OVER
:
32766
Sr.
No.
Parameters
Absolute
Address
Type
Access
Type
1
Input Type -1
40001
Int
R + W
2
Zero-1
40002
Int
R + W
3
Span-1
40003
Int
R + W
4
Filter
40004
Int
R + W
5
SET Type-1
40005
Int
R + W
6
SET Type-2
40006
Int
R + W
7
Open Sensor Status
40007
Int
R + W
8
Relay Delay -1
40008
Int
R + W
9
Hysteresis 1
40009
Int
R + W
10
Relay Delay -2
40010
Int
R + W
11
Hysteresis 2
40011
Int
R + W
12
Decimal Point-1
40012
Int
R + W
13
Display set point
40013
Int
R + W
14
Brightness
40014
Int
R + W
15
Serial Number
40015
Int
R + W
16
Baud Rate
40016
Int
R + W
17
Retransmission o/p Type
-1
40017
Int
R + W
18
Retransmission o/p
direction - 1
40018
Int
R + W
19
Retransmission o/p Type
-2
40019
Int
R + W
20
Retransmission o/p
direction - 2
40020
Int
R + W
21
Version
40033
Int
R