![Masibus LC5296 DC Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/masibus/lc5296-dc/lc5296-dc_user-manual_1735101028.webp)
Model: LC5296 Dual Channel Temperature Controller
Doc. Ref. no.:- m61C/om/101
Issue no. 01D/ENGG-114
User’s Manual
Page 28 of 30
Relay type
PV
Relay
LED
Hi-On
PV > SP
On
On
PV < SP
Off
Off
Open sensor Up scale
On
On
Down scale
Off
Off
Low-On
PV > SP
Off
Off
PV < SP
On
On
Open sensor Up scale
Off
Off
Down scale
On
On
10.3 Retramission Output Table for Open /Over /Under Condition
RETRASMISSION
VARIABLE SCALE
ACTION
OPEN
OVER
UNDER
4-20mA
PV
UP
DIR
20.8
20.8
3.2
PV
DOWN
REV
20.8
3.2
20.8
PV
UP
REV
3.2
3.2
20.8
PV
DOWN
DIR
3.2
20.8
3.2
1-5V
PV
UP
DIR
5.2V
5.2V
0.8V
PV
DOWN
REV
5.2V
0.8V
5.2V
PV
UP
REV
0.8V
0.8V
5.2V
PV
DOWN
DIR
0.8V
5.2V
0.8V
NOTE
: -1. OPEN/UNDER/OVER condition is applicable to all input types except
0-5v / 0-20mA.
10.4 Mapping Table for Relay and Retransmission Conditions
Mapping for
Parameters
Mapping
Options
Description
Relay
RL-1
IN 1
Relay - 1 for Process value 1
IN 2
Relay - 1 for Process value 2
RL-2
IN 1
Relay - 2 for Process value 1
IN 2
Relay - 2 for Process value 2
Retransmission
RT-1
IN 1
Retransmission - 1 for Process value 1
IN 2
Retransmission - 1 for Process value 2
RT-2
IN 1
Retransmission - 2 for Process value 1
IN 2
Retransmission - 2 for Process value 2