Model: LC5296 Dual Channel Temperature Controller 

 

 

 

Doc. Ref. no.:- m61C/om/101 
Issue no. 01D/ENGG-114 

 

 
User’s Manual

                                                                                                Page 11 of 30       

 

 
 
 
 
 
 
 

 
Fig 4.5: Lead Termination Detail 
 

4.2    How to connect wires? 

Before  carrying  out  wiring,  turn  off  the  power  to  the  controller  and  check  that  the 
cables to be connected are not alive because there is a possibility of electric shock. 

 
 

NOTE:

 

 

 

All  wiring  must  confirm  to  appropriate  standards  of  good  practice  and  local 
codes  and  regulations.  Wiring  must  be  suitable  for  Voltage,  Current  and 
temperature rating of the system. 

 

Provide power from a single-phase instrument power supply. If there is a lot of 
noise  in  the power line,  insert an insulating transformer into the primary side 
of the line and use a line filter on the secondary side. Do not place the primary 
and secondary power cables close to each other. 

 

For  RTD  input,  use  shielded  wires  that  have  low  conductor  resistance  and 
cause no significant differences in resistance between the three wires.  

 

Use  repeater  after  each  set  of  32  instruments  connected  in  RS-485 
Communication. 

 

Unused  terminals  should  not  be  used  as  jumper  points  as  they  may  be 

internally connected, which may cause damage to the unit. 

 

Unused control terminals should  not be used as jumper points as they may 
be internally connected, which may cause damage to the unit. 

 

Use >250V-1Amp Cable for Power Supply. 

 

Supply voltage must be below maximum voltage rating specified on the label 

 

If  cable  has  two  parallel  wires  inside  then  isolation  between  them  must  be 

2.5 KV. 

 

Содержание LC5296 DC

Страница 1: ...u ua al l C Ch ha an nn ne el l T Te em mp pe er ra at tu ur re e C Co on nt tr ro ol ll le er r Masibus Automation Instrumentation Pvt Ltd B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gu...

Страница 2: ...2 4 Communication Details 7 2 5 Power Supply 7 2 6 Environmental Conditions 8 2 7 Special Feature 8 3 PHYSICAL SPECIFICATIONS MOUNTING DETAILS 9 4 TERMINAL CONNECTIONS 10 10 4 2 How to connect wires...

Страница 3: ...PROTOCOL MODBUS RTU 25 9 1 Introduction 25 9 2 Parameter Address Details 25 9 3 Exceptional Response 26 10 APPENDIX 27 10 1 Troubleshooting 27 10 2 On Off Logic 27 10 3 Retramission Output Table for...

Страница 4: ...whole be transcribed or copied without our permission Trademarks Our product names or brand names mentioned in this manual are the trademarks or registered trademarks of Masibus Automation and Instru...

Страница 5: ...anual describe important information to prevent possible harm to users and damage to the property and to use the product safely Understand the following description signs and symbols read the text and...

Страница 6: ...iring resistance for RTD Maximum 15 ohms wire Conductor resistance between three wires should be equal NMRR 40 dB CMRR 120 dB Temp co 150ppm C Input Impedance 1M Voltage Input 250 Current Input Max Vo...

Страница 7: ...ire Protocol Modbus RTU Baud rate 9600 19200 38400 bps 2 5 Power Supply Standard 85 265VAC 100 300VDC Optional 18 36VDC Power consumption 10VA Data backup Non volatile memory can be written up to 1000...

Страница 8: ...onditions TEMPCO For Input 1 to PV1 Display 100ppm For Input 2 to PV2 Display 100ppm Humidity 30 to 95 RH Non Condensing Instrument Warm up Time Approx 15 minutes Ambient temperature 0 to 55 C Storage...

Страница 9: ...s Manual Page 9 of 30 3 PHYSICAL SPECIFICATIONS MOUNTING DETAILS Front Bezel 96 x 96 mm Panel Cutout 92mm 0 8 x 92mm 0 8 Depth Behind The Panel 65 mm with Terminal Weight 300g Approx Enclosure Materia...

Страница 10: ...al free Contacts Use 230V 2A load On Off Control o p 8 Earth Earth Connection 9 N 10 L Power Supply Input 11 24 LPS C 24VDC Loop power supply Terminal 13 is ground Reference or for RTD input 1 Three w...

Страница 11: ...insulating transformer into the primary side of the line and use a line filter on the secondary side Do not place the primary and secondary power cables close to each other For RTD input use shielded...

Страница 12: ...Model LC5296 Dual Channel Temperature Controller Doc Ref no m61C om 101 Issue no 01D ENGG 114 User s Manual Page 12 of 30 Fig 4 4 RS485 Connection Details...

Страница 13: ...nt Key Decrement the Value of any Parameter Shows ambient value for T C Input in RUN mode SET 1 Key Menu Enter Key Shows Set Point 1 ST 1 if pressed in RUN mode In Sub Menu it can be used to get to th...

Страница 14: ...ay Model Only Display error message when an error occurs PV 2 Process Value Display PV2 4 digital 0 56 inch RED Display process value for Input 2 Display parameter value of parameter in process value...

Страница 15: ...Model LC5296 Dual Channel Temperature Controller Doc Ref no m61C om 101 Issue no 01D ENGG 114 User s Manual Page 15 of 30 6 MENU LAYOUT...

Страница 16: ...Range Depending on PV sensor type selected 200 Parameter PV display Setting Name Description Default Value Show if Only Symbol Name INPT in 1 INPUT Type Set PV Input 1 Type rtd 1 rtd 0 5v 1 5v Value...

Страница 17: ...the SPAN Value 1999 If 0 5 V SPN 2 spn 2 Span 2 Automatically change to the Input Higher Range with changing of Input Type Refer Above Table Can be set to any value within the Input Range greater the...

Страница 18: ...Unit ID for Modbus RS485 Communication 1 to 247 1 If Device Supports RS 485 Communicatio n BAUD baud Baud Rate Set Modbus RS485 Communication Baud Rate 9600 19 2k 38 4k 0 9600 9600 bps 1 19 2K 19200...

Страница 19: ...2 rt 2 Retransmission 2 Type Retransmission 2 Output Type This output is according to PV input Zero Span acts as Min Max value of retransmission o p scale respectively 0 5v 1 5v 0 10 4 20 0 20 0 0 5V...

Страница 20: ...put with DP 1 0 01 to 1 00 Linear Input with DP 2 0 001 to 0 100 Linear Input with DP 3 5 PASS pass Password Set Device Password 0 to 99 1 VERS vers Version Shows the Version of the Current Firmware M...

Страница 21: ...V Input 1 PV Display Current PV CZ 2 CZ 1 Calibration Zero 2 Calibration Zero for PV Input 2 PV Display Current PV CS 2 CS 2 Calibration Span 2 Calibration Span for PV Input 2 PV Display Current PV RT...

Страница 22: ...Model LC5296 Dual Channel Temperature Controller Doc Ref no m61C om 101 Issue no 01D ENGG 114 User s Manual Page 22 of 30 Examples How to change Input Type...

Страница 23: ...point to above and back below In cases where this cycling occurs rapidly and to prevent contactors and valves from getting damaged an on off differential or hysteresis is added to the controller oper...

Страница 24: ...KEY Now press SET to store the calibration parameter in non volatile memory Similarly one can calibrate Ambient SPAN and retransmission parameters 8 2 Procedure for RET zero and RET span For calibrati...

Страница 25: ...sters 06 Preset Single register Use to write programmable register The error checking field contains a 16 bit value implemented as two eight bit bytes The error check value is the result of a Cyclical...

Страница 26: ...etransmission 1 Map 40027 Int R W 9 3 Exceptional Response CODE MEANING 01 Function code Invalid It must be 01 05 03 or 06 The function code received in the query is not allowable action for the slave...

Страница 27: ...10 APPENDIX 10 1 Troubleshooting If the operating display does not appear after turning on the controller s power follow the measures in the procedure below If a problem appears complicated contact o...

Страница 28: ...3 2 3 2 20 8 PV DOWN DIR 3 2 20 8 3 2 1 5V PV UP DIR 5 2V 5 2V 0 8V PV DOWN REV 5 2V 0 8V 5 2V PV UP REV 0 8V 0 8V 5 2V PV DOWN DIR 0 8V 5 2V 0 8V NOTE 1 OPEN UNDER OVER condition is applicable to all...

Страница 29: ...on PCB of Signal Card Among them One Slot is fixed for Retransmission Analog Output And the other Slot can be used for either Retransmission or RS 485 Communication Card by appropriate Jumper setting...

Страница 30: ...on card m61Cao201 Jumper Setting for Retransmission card m61Cao102 10 6 Load connection Electrical precautions during use Electrical noise generated by switching of inductive loads can create momentar...