background image

Doc.Ref. No. m61C/QG/501         Issue No.:00 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 1 of 2 

 

 

 

DIGITAL INDICATOR 

SPECIFICATIONS 

 

Input type 

Range 

PT100 (0.1

º

C)    

-199.9 to 850.0 

º

PT100 (1

º

C)    

 -200  to  850

º

 -199.9  to 1200

º

 -199.9  to 1372

º

 -199.9  to 400

º

    0   to 1768

º

    0   to 1768

º

*4-20mA /1-
5VDC 

-1999 to 9999  
(Field Scalable) 
 

*0-20mA /0-
5VDC 
0-10VDC 

*Use external 250ohms, 0.1% for current Input 

Table 1.1 

Inputs 

Input Type 

Thermocouple, RTD 
(Pt100), Current, Voltage 

Accuracy 
T /C and RTD : 
Linear: 

 
+0.25% of FS + 1 degree  
+0.1% of FS + 1 count 

Resolution 

ADC:16bits 
Display:0.1°C/1°C  

Sampling Rate 

5 Samples/Sec 

CJC Error 

±2.0 °C Max 

Sensor Burnout 
current 

0.25uA 

RTD excitation 
current 

0.166mA (Approx.) 

Allowable 
wiring 
resistance for 
RTD 

Maximum 15 ohms/wire 
(Conductorresistance 
between three wires 
should be equal) 

NMRR 

> 40 dB  

CMRR 

> 120 dB  

Input 
Impedance 

> 1MΩ (Voltage Input) 
250Ω (Current Input)  

Max Voltage 

20VDC 

 

Display & Keys 

PV 

4-Digit 7-Segment, 0.8”  High,Red 

Keys  Enter,Increase,Decrease 

 

Output Types 

Loop Power 
Supply 

24VDC (±10%) 
@26mAwith Inbuilt Short 
Circuit Protection 

 

Power Supply 

 

Standard 

85-265VAC/ 100-
300VDC  

Optional 

18-36VDC  

Power 
consumption 

<5VA  

 

Isolation (Withstanding voltage) 

 

Between primary terminals* and secondary 

terminals**:  
At least 1500 V AC for 1 minute  

 

Between primary terminals* and grounding 

terminal: 
At least 1500 V AC for 1 minute  

 

Between grounding terminal and secondary 

terminals**: 
At least 1500 V AC for 1 minute 

 

Between secondary terminals**: 

At least 500 V AC for 1 minute 
* Primary terminals indicate power terminals 
and relay output terminals. 
** Secondary terminals indicate analog I/O 
signal and Communication O/P. 
Insulation resistance: 20MΩ or more at 500 
V DC between power terminals and grounding 
terminal. 

 

Physical

 

Dimension 

(WxHx D)mm 

 

96 x 48 x 85 

Front Bezel(H x W)mm 

48 x 96 

Panel Cutout mm 

92 x 46 

Depth Behind Panel mm  75 
Weight Approx. 

260g.  

Enclosure Material 

ABS Plastic 

Enclosure Protection 

IP 20 

Terminal Cable Size  

2.5mm

2

 

Environmental Conditions

 

TEMPCO 

< 100ppm/°C 

Humidity 

20% to 95% RH  
(Non-Condensing) 

Ambient 
temperature 

0 to 55°C 

Storage 
Temperature 

0 to 80°C 

 

Advance Feature 

 

Input scalability for linear input 

 

MOUNTING DETAILS 

 

 
ORDERING CODE 

 

 

 
TERMINAL CONNECTIONS 

 

Terminal No. 

Description 

1   LPS+ 

24VDC Loop power 

supply Terminal 4 is 
ground Reference. 

2   C+ 

For RTD Input Only 
(Three wire 

Compensation). 

3  TC+/ V+ 

For Thermocouple, RTD 
&Linear Input 

4  TC- / V- / LPS- 
9   L/+ 

Power Supply Input 

10 N/- 

 

 

 
SAFETY/WARNING PRECAUSTIONS 
 

To  ensure  that  the  device  can  be  operated 
safely and all functions can be used, please read 
these instructions carefully. 
Installation and Start-up must be carried out by 
qualified  personnel  only.  The  relevant  county-
specific regulations must also be observed. 
Before  start-up  it  is  particularly  important  to 
ensure: 

 

Terminal  wiring:  check  that  all  cables  are 

correctly connected according to the connection 

diagram 

 

All  wiring  must  confirm  to  appropriate 

standards  of  good  practice  and  local  codes  and 
regulations. Wiring must be suitable for voltage, 

current and temperature rating of the system. 

 

Unused  control  terminals  should  not  be  used 

as  jumper  points  as  they  may  be  internally 

connected,  which  may  cause  damage  to  the 
unit. 

 

FRONT PANEL DESCRIPTION 

 

Name of 

Part 

Symbol  Function 

 

Increment 

Key 

 

 

Increment the 

Value of any 
Parameter in edit 

mode. 

 

Shuffle to next 

parameter in the 

Sub Menu 

Quick User Guide 

 

408-M 

Model 

Input 

Auxiliary Power 

Supply 

408-M  1 

U1 

85-265 VAC / 
100-300 VDC 

  

  

U2  18-36 VDC 

  

 

 

  

 
 

 
 

  

Pt-100 

  

C  4-20mA 

 

 

  

D  0-20mA 

 

 

  

1-5 V 

 

 

  

0-5 V 

 

 

  

G  0-10 V 

 

 