User Manual
37
40005E (Enhanced Bargraph Indicator)
REF NO: m42B/om/101
Issue No:02
In above example
Process Value on Display varies between:
1. 0
– 1000 for input of 0 % – 10%
2. 1000
– 2000 for input of 10% – 20%
3. 2000
– 3000 for input of 20 % – 30%
4. 3000
– 4000 for input of 30 % – 40%
5. 4000
– 5000 for input of 40 % – 50%
6. 5000 - 6000 for input of 50 % - 60 %
7. 6000
– 7000 for input of 60 % – 70%
8. 7000
– 8000 for input of 70 % – 80%
9. 8000
– 9000 for input of 80 % – 90%
10. 9000
– 9999 for input of 90 % – 100%
5 point Linearization:
Zero = 00000 and Span = 9999, Let us assume the Unit is 4-20 mA.
Table 13 5 - Point Linearization
In above example
Process Value on Display varies between:
1. 0
– 2000 for input of 0 % – 10%
2. 2000
– 4000 for input of 10% – 50%
3. 4000
– 4500 for input of 50 % – 60%
4. 4500
– 7500 for input of 60 % – 80%
5. 7500
– 9999 for input of 80 % – 100%
Similarly, the configuration of Linearization is done for 2,3,4,6,7,8,9 points.
To enable and Disable Linearization use the Ln.En parameter.
Configuration of linearization percent, range and Linearization Enable/Disable function is individual for
both channels.
8
LP08
80%
LR08
8000
16.8
9
LP09
90%
LR09
9000
18.4
10
LP10
100%
LR10
9999
20
Step No.
Linearization
Percent
Value
Linearization
Range
Display Value
Input Current
mA
1
LP01
10%
LR01
2000
5.6
2
LP02
50%
LR02
4000
12.0
3
LP03
60%
LR03
4500
13.6
4
LP04
80%
LR04
7500
16.8
5
LP05
100%
LR05
10000
20
6
LP06
0
LR06
0
7
LP07
0
LR07
0
8
LP08
0
LR08
0
9
LP09
0
LR09
0
10
LP10
0
LR10
0