18
After entering -- C page, set the communication protocol. The display screen protocol display is
represented by three hexadecimal digits. The first number represents RS485 protocol, the second
number is reserved, and the third number is CAN protocol option, as shown in the below picture.
The detailed steps of modifying the agreement are as follows:
1. The inicial page displays the default protocol of the battery. If it needs to be modified, first click
"Enter" and the first number is in the flashing state. At the time, enter the RS485 protocol selection
state. Select the corresponding number or letter through the "up" key / "down" key and compare with
the
Communication Protocol List
in the above table, so as to select corresponding inverter protocol
(RS485) is required. The selection numbers/letters range is 15 bits(0-D).
2. After selecting RS485 protocol, click "Enter" to automatically jump to the third number. At the
time, the third number is in flashing state and enters the CAN protocol selection state. The selection
range is 15 bits(0-D). Select corresponding inverter protocol (CAN) is required by pressing "up" key
/ "down" key and referring to the number or letter corresponding to the
Communication Protocol
List
.
3. After selecting the CAN protocol, you need to click the "enter" key. After a few seconds, the
protocol is successfully replaced and saved without power on again.
4.3.2 Setting By BMS Host Software(PC)
BMS Host software need to install with PC. Log in to our website or consult the local dealer to obtain
the BMS upper computer software, but we suggest that the upper computer software should be used
by professional installers.
When connect the Master or RS485 communication port from the battery to a computer, the host
software information displays on 7 different tabs:
Home: SOC%, voltage, current, cycles, capacity and running status, cell balancing
,
temperature
Date: Real Data Recode
RS485
CAN