Conditions
Possible cause
Action
Line input different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E7
Parallel system
,
UPS1 line ok
,
UPS2 line loss
Check the line input
Power strategy different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E9
Parallel system
,
UPS mode
(
normal
,
converter
,
HE
)
different
Check UPS OP mode, Keep OP mode
be the same
Rate power different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0EA
Parallel system rate power
different
Rate power different
,
not allow
turn on UPS. Keep rate power be the
same
HE in parallel
Fault (Red) LED is flash
1 beep every 1 second
Code: A0EB
Parallel system
,
UPS mode set
as HE
HE not allow in parallel system
,
change UPS mode
8.2 Silencing the alarm
Press the ESC (Escape) button 3s on the front panel display to silence the alarm. Check
the alarm condition and perform the applicable action to resolve the condition. If the
alarm status changes or press the ESC button 3s on the front panel display, the alarm
beeps again, overriding the previous alarm silencing.