24
The following table shows the Control Button Functions:
The Button
Function
Illustration
Power on
Press this button for >100ms&<1s can power on the
ups without utility input at the condition of battery
connected.
Turn on
When the unit is powered on and stayed is in Bypass
mode, press this button for >1s can turn on the UPS.
Turn off
Press this button >3s can turn off the UPS.
Clear fault
When the unit is in fault mode, press this button
for >1s to stop alarm and clear fault
Scroll up
Press this button for >100ms&<1s to scroll up the
menu option
Scroll down
Press this button for >100ms&<1s to scroll down the
menu option
Enter next menu
tree
Press this button for >100ms&<1s to select the present
menu option, or enter next menu, but do not change
any setting
Select one
menu option
Press this button for >100ms&<1s to select the present
menu option, or enter next menu, but do not change
any setting
Confirm the
present setting
Press this button for >1s to confirm the edited options
and change the setting
Exit main menu
Press this button for > 100ms & < 2s to exit the present
menu to default system status display menu or the
higher level menu without executing a command or
changing a setting
Mute buzzer
Press this button for > 2s to mute the buzzer
temporarily, once new warning /fault is active or UPS
reenters into bypass mode or battery mode, buzzer will
work again.