4.3 Alarm List
In Table 4-12, it provides the complete list of UPS alarm messages.
Table 4-12: Alarm List
Representation in display LCD
Explanation
Fault! Bus Over Voltage
DC bus voltage is too high
Fault! Bus Under Voltage
DC bus voltage is too low
Fault! Bus Voltage Unbalance
DC bus voltage is not balanced
Fault! Bus Short
DC bus is short
Fault! Bus Soft Start Time Out
The rectifiers can’t start due to low DC bus voltage
within specified duration
Fault! Inverter Soft Start Time Out
Inverter bus voltage cannot reach desired voltage
within specified duration
Fault! Inverter Voltage Over
Inverter Voltage is over Peak Value.
Fault! Inverter Voltage High
Inverter Voltage is too high
Fault! Inverter Voltage Low
Inverter Voltage is too Low
Fault! R Inverter Voltage Short
R phase inverter Output is short-circuited.
Fault! S Inverter Voltage Short
S phase inverter Output is short-circuited.
Fault! T Inverter Voltage Short
T phase inverter Output is short-circuited.
Fault! RS Inverter Voltage Short
R-S inverter Output is short-circuited.
Fault! ST Inverter Voltage Short
S-T inverter Output is short-circuited.
Fault! TR Inverter Voltage Short
T-R inverter Output is short-circuited.
Fault! Inverter R Negative Power
R phase inverter Output Negative Power over range
Fault! Inverter S Negative Power
S phase inverter Output Negative Power over range
Fault! Inverter T Negative Power
T phase inverter Output Negative Power over range
Fault! Over Load Fault
Heavy overload causes UPS fault.
Fault! Battery Fault
Batteries reversed
Fault! Over Temperature
Make sure adequate space is allowed for air ventilation
and the fan is working
Fault! CAN Fault
CAN communication fault
Fault! TRIG0 Fault
Synchronized trigger signal fault
Fault! Relay Fault
Inverter relay fault
Fault! Line SCR Fail
Line SCR short circuit fault
Fault! EEPROM Fault
EEPROM operation error
Fault! Parallel Cable Loosen Fault
As stated.
Fault! DSP MCU Stop Communicate
As stated.
Fault! Bypass Temperature Fault
As stated
Fault! Bypass SCR Fault
As stated.
Line Fail
Utility lost or abnormal
Line Restore
Utility recovered to normal
Warning! EPO Active
Check the EPO connector
Warning! Over Load Fail
The load devices are demanding more power than the
UPS can supply. Line mode will transfer to Bypass
mode.
Warning! Communicate CAN Fail
CAN communication error
Warning! Over Load
In Line mode, the load devices are demanding more
power than the UPS can supply.
Warning! Battery Open
Battery not connected
Warning! Battery voltage High
Battery voltage is too High
Warning! Module Un-Lock
As stated.
Содержание Matrix VX33 Series
Страница 13: ...10 Figure 2 7 Dimensions...
Страница 45: ...42 Figure 4 7 Control screen page 1 Figure 4 8 Control screen page 2...
Страница 66: ...63 Figure 4 41 Reset All Events screen Figure 4 42 Reset All Events Confirmation screen...
Страница 88: ...85 Step 3 Take out the frame by removing screws Step 4 Pull out the battery try and replace inside batteries...