INSTRUCTIONS

THERMO ANEMOMETER

AV90

SPECIFICATIONS AND FEATURES

A. Portable digital Thermo-Anemometer.

B. Simultaneous display of both temperature and air speed.

C. Memory of maximum, minimum and average record for both temperature

and wind speed.

D. Air velocity average for multiple points.

E. Auto power off function.

F. 2 meter coiled cable and mounting nut for long extension.

GENERAL

Low battery indication: The "      " is displayed when the battery voltage drops

below the operating level

Accuracy:

Stated accuracy at 23°C ± 5°C, <80% relative humidity

Operating environment:

0°C to 50°C at <75% relative humidity

Storage environment:

-20°C to 55°C at <80% relative humidity

Battery:

Standard 9V battery (NEDA 1604, IEC 6F22 006P)

Battery Life:

200 hours typical with carbon zinc battery

Dimensions:

770(H) x 65.5(W) x 35mm(D) 

Weight:

390g including battery and probe

MAX MIN Record Mode

Press MIN/MAX button to enter the MIN MAX Recording mode. In this

mode, the automatic power off feature, °C/°F button & UNIT buttons are

disabled, and the measurement period will be set to 2 seconds.

Push MIN MAX key to cycle through the MAX (maximum), MIN (minimum),

MAX -MIN (maximum minus minimum) and AVG (average) readings. In this

2

mode, press the HOLD key to stop the recording of readings, all values are

frozen, press again to restart recording. Press and hold down the MIN MAX

button for 2 seconds, or press the RESET button to exit and erase recorded

readings.

2 sec. / 16 sec. Average Mode

Pressing the 2sec/16sec button sets the measurement period to 2 seconds.

"AVG 2" is displayed in the lower left hand side corner of the display. The first

reading will hold for two seconds and flash "2" on the display, and then update

every two seconds with average for the last two seconds. The default setting for

the measuring period is 2 seconds. Pressing the 2sec/16sec button again sets

the measurement period to 16 seconds. "AVG 16" is displayed in the lower left

hand side corner of the display. The first reading will hold for sixteen seconds

and flash "16" on the display, and then update every two seconds with average

for the last sixteen seconds.

Multi Point Average Mode

1. Place the probe head in the area where air velocity is to be measured.

Press the HOLD button to take the measurement and enter the data hold mode.

The anemometer holds the reading.

2. Press the MAX MIN button. The second display will show a count. This

number represents the point that is being recorded.

3. Repeat this process until all desired points have been measured and recorded.

4. Press the MULTI POINT button. This will display the average air velocity

reading and number of points measured. The anemometer can recorded a total

of 8 points at one time, and calculate the average for the last 8 points.

5. Press and hold down the MULTI POINT button or press the RESET button

for 2 seconds to exit and erase recorded readings, or press "HOLD" button to

exit but not erase recorded readings.

3

TEMPERATURE

Temperature Scale:

Celsius or Fahrenheit user-selectable

Temperature Sensor: 

NTC

Measurement Range:

-20°C to 60°C / -4°F to 140°F

Measurement rate:

1 times per second.

Resolution: 0.1°C/°

Accuracy:  ±1.0°C

on 

-20°C to 0°C, 45°C to 60°C

±0.5°C

on  

0°C to 45°C

±2.0°F

on  

-4°F to 32°F, 113°F to 140°

±1.0°F

on  

32°F to 113°F

Air Velocity

Mounting Nut: 

1/4" x 20

Operating Temperature:

Meter: 0°C to 50°C (32F to 122°F)

Vane: 0°C to 60°C (32F to 140°F)

WIND VELOCITY

Units

Resolution

Threshold

Range

m/s

0.01

0.3

0.0-30.0

ft/min

1

60

0.0-5900

knots

0.1

0.6

0.0-58.0

mph

0.1

0.7

0.0-67.0

Km/h

0.1

1.1

0.0-108.0

Accuracy: ±3%FS