Exterior
Wash
TM
100 Series User Manual
15
AC power
Warning! Read “Safety Information” on page 5 before attempting to install the
fixture. Lock out power to the entire installation before working on cables and
connections.
Electrical installation must be carried out by qualified professionals only.
For protection from dangerous electric shock, the fixture must be grounded (earthed). The
AC power distribution system must be fitted with current overload and ground-fault (earth-
fault) circuit breakers as well as a means to isolate fixtures from power and lock out power
during service.
The Exterior Wash
™
100 Series is supplied in EU and US models. Both models accept AC power at
100-240 V nominal or 277 V nominal at 50 or 60 Hz. Do not connect to power at any other voltage or
frequency.
You can connect the Exterior Wash 100 Series to either of the following mains power distribution systems:
●
Single-phase (live, neutral, ground/earth) system.
●
Grounded/earthed three-phase four-wire (three phases, neutral, ground/earth) system. s
Do not try to connect to a three-phase three-wire (three phases, ground/earth) system.
There is no power on/off switch. Power is applied to an Exterior Wash
™
100 Series fixture as soon as it is
connected to power. Provide a means to disconnect or shut down power to fixtures that is easily
accessible and is located close to the fixtures.
Do not use an external dimming system to supply power to the fixture, as this may cause damage to the
fixture that is not covered by the product warranty.
Protecting connections from moisture
Moisture can cause corrosion in unprotected cable connections. Moisture can also be sucked along the
inside of cables at breaks or cuts in the cable jacket (for example at connection points) and into fixtures
because of the vacuum effect of temperature fluctuations inside fixtures. To protect connections and
fixtures from moisture, take at least one of the following precautions:
●
Locate cable junctions in dry areas (e.g. junction boxes in dry locations).
●
Use connectors or junction boxes that are protected to IP67 or higher.
●
Fill junction boxes with potting compound to seal the ends of cables and to protect connections from
corrosion.
Connecting to power
The fixture is supplied with a power cable installed ready for connection. See illustration below:
AC power cable details
To connect to a single-phase system or to one phase of a three-phase four-wire system:
1. Lock out power to the installation.
2. Connect the conductors in the power cable to the distribution circuit inside a suitable junction box as
follows:
3. Connect the green wire (US models) or yellow/green wire (EU models) to ground (earth).
4. Connect the white wire (US models) or blue wire (EU models) to neutral.
5. Connect the black wire (US models) or brown wire (EU models) to live (one phase).
Содержание Exterior Wash 100
Страница 1: ...Exterior Wash 100 Series User manual...
Страница 4: ......
Страница 36: ...www martin com Olof Palmes All 18 8200 Aarhus N Denmark Tel 45 8740 0000 Fax 45 8740 0010...