SOLO-NX
EXT
INSTALLATION MANUAL
Page 12
9.2.2
OD parameter
OD parameter is used to link the alarm event directly to output.
9.2.3
OP1, OP2 parameters
Parameters are used to invert the polarity of the outputs.
0 – normal
1 – inverted
9.2.4
Table of parameters
Name
Comment
OS1
Mode of operation for output 1
OS2
Mode of operation for output 2
OD1
Input 1 direct link to outputs
OD2
Input 2 direct link to outputs
OD3
NAC direct link to outputs
OP1
Invert control for output 1
OP2
Invert control for output 2
Table 6: Output management parameters
Example:
Direct programming on the SIM card
SOLO-NX PROGRAMMING TABLE
Name
Number
Description
OS1
1
Bistable toggle mode
OS2
14
Monostable pulse mode (14s pusle)
OD1
1
Input 1 activates output 1
OD2
2
Input 2 activates output 2
OP1
1
Output 1 inverted
Table 7: Output management parameters example
Remote programming by SMS
;OS1=1;OS2=14;OD1=1;OD2=2;OP1=1;