background image

DOC-FW511-UM-R1.2 

INSTALLATION MANUAL 
 

© 2016. MAPLE ARMOR FIRE ALARM DEVICE CO., LTD.  

8866, boulevard du Quartier, Brossard, Quebec, Canada, J4Y 0R2  

All rights reserved. www.maplearmor.com 

Page 

1

 of 

2

 

 

FW511 Smoke Detector 

 

 

 

DESCRIPTION 

 
The FW511 is an intelligent Smoke Detector used with the 
FW500 Detector Base, is a UL listed component according 
to  UL  268  and  ULC-S529  for  Fire  Protective  Signaling 
Systems  for  indoor  use.  It  features  a  slim  design  which 
combines visual appeal with a high standard of reliability. It 
responds quickly and dependably to a broad range of fires. 
The detector has a Microcontroller Unit (MCU), performing 
comprehensive self-diagnostic tests and result analysis. The 
FW511 is intelligent, addressable, and takes one address on 
the  Signaling  Line  Circuit  (SLC)  of  the  fire  alarm  control 
panel. 

ATTENTION 

The products must be installed in accordance with NFPA 72, 

CAN/ULC-S524, and/or Canadian Electrical 
Code  depending  on  country  of  installation. 
Check information of equipment used in the 
system  by  other  manufacturers  for  any 
guidelines or restrictions.  

The detector should never be installed in the 
following locations: areas with excessive exhaust 
fumes, kitchen areas, near fireplaces, furnace rooms, 
etc. Smoke detectors are not to be used with detector 
guards unless the combination has been evaluated 
and found suitable for that purpose. 

 
NOTE 

Do not paint this device. 
Any  material  extrapolated  from  this  document  or  from 
Maple Armor’s instructions or other documents describing 
the product for use in promotional or advertising claims, or 
for  any  other  use,  including  description  of  the  product’s 
application,  operation,  installation,  and  testing  is  the  sole 
responsibility of the user. Maple Armor will not assume any 
liability for such use. In no case will Maple Armor’s liability 
exceed the purchase price paid for a product. 

 

SPECIFICATION 

Nominal Voltage 

24VDC 

Voltage Range 

17.6 to 25.5VDC 

Standby Current 

0.14mA 

Alarm Current 

1mA 

Smoke Sensitivity 

1.6% ft to2.3% ft 

Operating 
Temperature 

32°F to 100°F (0°C to 38°C) 

Operating Humidity  

0% to 93% RH 

Diameter 

4.13 in. (105mm) 

Height (with base)  

1.87 in. (47.5 mm) 

Weight (with base) 

4.6 oz (132 g) 

Mounting  

FW500 Base 

Mounting Orientation 

Ceiling, wall 

Spacing 

30 feet (9.1 m) 

SPECIFICATIONS  
INSTALLATION 
 

1.

 

Mount the FW500 base onto a 2x4’’ electrical 
box using the screws provided, see Figure 1. The 
installation hole pitch is illustrated in Figure 2. 

 

Figure 1. FW500 Base Installation 

 

Figure 2. Wiring Terminals and Pitch of Hole 

#6-32 Screw(2)
For 2X4" Electrical Box

2X4" Electrical Box