–81–
Cycle Times/24 Hour Ice Production
and Refrigerant Pressure Charts
These charts are used as guidelines to verify correct
ice machine operation.
Accurate collection of data is essential to obtain the
correct diagnosis.
•
Refer to “OPERATIONAL ANALYSIS CHART” for
the list of data that must be collected for refrigeration
diagnostics. This list includes: before beginning
service, ice production check, installation/visual
inspection, water system checklist, ice formation
pattern, safety limits, comparing evaporator inlet/
outlet temperatures, hot gas valve analysis,
discharge and suction pressure analysis.
•
Ice production checks that are within 10% of the
chart are considered normal. This is due to
variances in water and air temperature. Actual
temperatures will seldom match the chart exactly.
•
Zero out manifold gauge set before obtaining
pressure readings to avoid misdiagnosis.
•
Discharge and suction pressure are highest at the
beginning of the cycle. Suction pressure will drop
throughout the cycle. Verify the pressures are within
the range indicated.
Содержание UG018A
Страница 2: ......
Страница 6: ...This Page Intentionally Left Blank ...
Страница 12: ... 2 This Page Intentionally Left Blank ...
Страница 20: ...10 Evaporator Spray Nozzles Toggle Switch Spray Bar Ice Chute ...
Страница 36: ...26 dip switch Decrease Cube Size Factory Default Setting Increase Cube Size test button ...
Страница 37: ...27 CUBE SHAPE The standard cube has an average weight of 19 Notice the normal dimple in the center of the cube ...
Страница 38: ...28 ...
Страница 80: ...70 This Page Intentionally Left Blank ...
Страница 128: ... 118 This Page Intentionally Left Blank ...
Страница 135: ... 125 ...