
22
Electrical Service
n
Warning
All wiring must conform to local, state and national
codes.
VOLTAGE
The maximum allowable voltage variation is ± 10% of the
rated voltage on the ice machine model/serial number
plate at compressor start-up.
FUSE/CIRCUIT BREAKER
A separate fuse/circuit breaker must be provided for each
ice machine. Circuit breakers must be H.A.C.R. rated (does
not apply in Canada).
n
Warning
The ice machine must be grounded in accordance with
national and local electrical codes.
GROUND FAULT INTERRUPTER CIRCUIT (GFIC)
A GFCI/GFI circuit protection is not recommended with
our equipment. If a GFCI/GFI is required by code a GFCI/
GFI breaker rather than outlet must be used to avoid
intermittent nuisance trips.
Содержание RFF
Страница 2: ......
Страница 34: ...THIS PAGE INTENTIONALLY LEFT BLANK 34 Part Number 000015433_03 5 20 ...
Страница 146: ...THIS PAGE INTENTIONALLY LEFT BLANK 146 Part Number 000015433_03 5 20 ...
Страница 152: ...152 Part Number 000015433_03 5 20 RFF1220C RCUF1000 CONDENSING UNIT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 ...
Страница 160: ...THIS PAGE INTENTIONALLY LEFT BLANK 160 Part Number 000015433_03 5 20 ...
Страница 161: ......
Страница 162: ......
Страница 163: ......