170
Part Number 000014797 Rev02 05/18
ANALYZING DISCHARGE LINE TEMPERATURE
1. Determine the ice machine operating conditions:
Air temperature entering condenser
______
Air temperature around ice machine
______
Water temperature entering sump trough ______
2. Refer to “Installation/Visual Inspection Checklist” on
page 164 for ice machine being checked.
Use the operating conditions determined in step 1 to find
the published normal discharge temperatures.
Freeze Cycle
______
Harvest Cycle
______
3. Perform an actual discharge temperature check.
Freeze Cycle
Temperature
Harvest Cycle
Temperature
Beginning of
Cycle
__________
__________
Middle of
Cycle
__________
__________
End of
Cycle
__________
__________
4. Compare the actual discharge temperature (Step 3)
with the published discharge temperature (Step 2).
The discharge temperature is normal when the actual
temperature falls within the published temperature range
for the ice machine’s operating conditions. It is normal for
the discharge temperature to be lower at the beginning of
the freeze cycle, then climb through out the freeze cycle.
Содержание NEO UD0140A
Страница 2: ......
Страница 20: ...20 Part Number 000014797 Rev02 05 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 182: ...182 Part Number 000014797 Rev02 05 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 215: ...Part Number 000014797 Rev02 05 18 215 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING Using Pinch Off Tool ...
Страница 252: ...252 Part Number 000014797 Rev02 05 18 ELECTRONIC CONTROL BOARD UDE065 1 2 3 4 5 6 ...
Страница 254: ...254 Part Number 000014797 Rev02 05 18 ELECTRONIC CONTROL BOARD UDE080 1 2 3 4 5 6 7 8 9 10 ...
Страница 258: ...258 Part Number 000014797 Rev02 05 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 259: ......