background image

 K00133/K00134 MAC-7 and MAC-8 

                                             HEADMASTER KITS

 

                                                              Installation Instructions 

 
 

IMPORTANT - Refrigerant line lengths must not exceed 50 feet. 
 

1.

 

Lubricate the female fittings with refrigerant oil and install the assembly of the quick-connect fittings on the MAC-7 
or MAC-8 condensing unit. 

2.

 

The metal enclosure attaches to the MAC-7 or MAC-8 condensing unit with three screws from the unit, two screws on 
top and one screw at the bottom. 

3.

 

The remote tubing line set attaches to the male fittings provided on the headmaster kit.  Refrigerant oil must be used 
to lubricate the fittings. 

4.

 

Leak check all joints. 

5.

 

Place the four labels, 8136193, included, as follows:  two on the ice machine (one by each serial plate), one, as shown 
below, and one at the discretion of the installer. 

6.

 

ATTENTION INSTALLER:

  Add the following refrigerant at the time of installation: 

Q-0600 Series - add four (4) pounds 
Q-0800 Series - add four (4) pounds 
Q-1000 Series - add two (2) pounds 
Q-1300 Series - Add nothing 

 
  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Manitowoc Ice, Inc.                                                                                                                                                               

2110 South 26 Street, P.O. Box 1720, Manitowoc, WI  54221-1720 USA  
Telephone 920-682-0161, Fax - Sales:  920-683-7589, Service/Parts: 920-683-7585,  Other:  920-683-7879                                                8010113 
Web Site - 

www.manitowocice.com

                                                                                                                                                          Rev. 06/28/01 

Отзывы: