Mandik VCDM Скачать руководство пользователя страница 6

Volume control damper - VCDM

Page 6

Version 2023-02-14

TPM 167/23

Technical parameters

A x B

[mm]

Number of

blades

Weight

[kg]

Effective

area Sef

[m

2

]

A x B

[mm]

Number of

blades

Weight

[kg]

Effective

area Sef

[m

2

]

200 x

200

1

14,3

0,0227

400 x

200

1

17,6

0,0511

250

2

16,4

0,0270

250

2

20,3

0,0608

300

2

17,3

0,0350

300

2

21,5

0,0788

350

2

18,3

0,0430

350

2

22,6

0,0968

400

2

19,2

0,0510

400

2

23,8

0,1148

450

3

21,2

0,0554

450

3

26,4

0,1246

500

3

22,2

0,0634

500

3

27,6

0,1426

600

3

24,1

0,0794

600

3

30,0

0,1786

700

4

27,0

0,0917

700

4

33,7

0,2063

800

4

28,9

0,1077

800

4

36,1

0,2423

900

5

34,5

0,1200

900

5

42,5

0,2700

1000

5

36,4

0,1360

1000

5

44,8

0,3060

1100

6

39,3

0,1483

1100

6

48,6

0,3337

1200

6

41,2

0,1643

1200

6

51,0

0,3697

250 x

200

1

15,1

0,0298

450 x

200

1

18,4

0,0582

250

2

17,4

0,0355

250

2

21,3

0,0693

300

2

18,4

0,0460

300

2

22,5

0,0898

350

2

19,4

0,0565

350

2

23,7

0,1103

400

2

20,4

0,0670

400

2

25,0

0,1308

450

3

22,5

0,0727

450

3

27,7

0,1419

500

3

23,5

0,0832

500

3

28,9

0,1624

600

3

25,5

0,1042

600

3

31,4

0,2034

700

4

28,7

0,1203

700

4

38,0

0,2349

800

4

30,7

0,1413

800

4

40,5

0,2759

900

5

36,5

0,1575

900

5

44,5

0,3075

1000

5

38,5

0,1785

1000

5

47,0

0,3485

1100

6

41,6

0,1947

1100

6

50,9

0,3801

1200

6

43,6

0,2157

1200

6

53,4

0,4211

300 x

200

1

15,9

0,0369

500 x

200

1

19,2

0,0653

250

2

18,3

0,0439

250

2

22,2

0,0777

300

2

19,4

0,0569

300

2

23,5

0,1007

350

2

20,5

0,0699

350

2

24,8

0,1237

400

2

21,5

0,0829

400

2

26,1

0,1467

450

3

23,8

0,0900

450

3

29,0

0,1592

500

3

24,9

0,1030

500

3

30,3

0,1822

600

3

27,0

0,1290

600

3

32,9

0,2282

700

4

30,3

0,1490

700

4

39,7

0,2636

800

4

32,5

0,1750

800

4

42,3

0,3096

900

5

38,5

0,1950

900

5

46,5

0,3450

1000

5

40,6

0,2210

1000

5

49,1

0,3910

1100

6

43,9

0,2410

1100

6

53,2

0,4264

1200

6

46,1

0,2670

1200

6

55,8

0,4724

350 x

200

1

16,8

0,0440

600 x

200

1

20,9

0,0795

250

2

19,3

0,0524

250

2

24,2

0,0946

300

2

20,4

0,0679

300

2

25,6

0,1226

350

2

21,6

0,0834

350

2

27,0

0,1506

400

2

22,7

0,0989

400

2

28,4

0,1786

450

3

25,1

0,1073

450

3

31,6

0,1938

500

3

26,2

0,1228

500

3

33,0

0,2218

600

3

28,5

0,1538

600

3

35,8

0,2778

700

4

32,0

0,1776

700

4

43,1

0,3209

800

4

34,3

0,2086

800

4

45,9

0,3769

900

5

40,5

0,2325

900

5

50,5

0,4200

1000

5

42,7

0,2635

1000

5

53,3

0,4760

1100

6

46,3

0,2874

1100

6

57,9

0,5191

1200

6

48,5

0,3184

1200

6

60,7

0,5751

Содержание VCDM

Страница 1: ...dik mandik cz Manufacturer MANDIK UK Ltd 130 Aztec West Bristol BS32 4UB United Kingdom Tel 44 117 4526376 E Mail help mandik co uk Authorized representative VCDM Volume control damper Technical Documentation Installation Commissioning Operation Maintenance and Service Manual TPM 167 23 Version 2023 02 14 ...

Страница 2: ...Description 3 Design 4 Design with manual control 4 Dimensions 5 Technical parameters 6 Placement and Assembly 7 II TECHNICAL DATA 8 Pressure loss 8 Noise data level of acoustic output corrected with filter A 9 III MATERIAL FINISHING 10 Material 10 IV INSPECTION TESTING 10 V TRANSPORTATION AND STORAGE 10 Logistic terms 10 VI ASSEMBLY ATTENDANCE AND MAINTENANCE 11 Assembly 11 Entry into service and...

Страница 3: ...es Dampers are suitable for systems without abrasive chemical and adhesive particles Dampers are designed for macroclimatic areas with mild climate according to EN IEC 60 721 3 3 ed 2 class 3K22 Temperature in the place of installation is permitted to range from 20 C to 50 C The Mandik VCDM is a volume control damper suitable for use at high temperatures The VCDM can be used to control and balance...

Страница 4: ... damper VCDM Page 4 Version 2023 02 14 TPM 167 23 Design Design with manual control Design with manual control with which actuates the shutting device Design 01 Design 01 Damper blades is closed Damper blades is open ...

Страница 5: ...ge 5 Version 2023 02 14 Volume control damper VCDM TPM 167 23 Dimensions 1 Damper body 2 Damper blade 3 Manual control Flange with corner hole Flanges of dampers are 30 mm wide with oval hole Damper VCDM ...

Страница 6: ...0 4 38 0 0 2349 800 4 30 7 0 1413 800 4 40 5 0 2759 900 5 36 5 0 1575 900 5 44 5 0 3075 1000 5 38 5 0 1785 1000 5 47 0 0 3485 1100 6 41 6 0 1947 1100 6 50 9 0 3801 1200 6 43 6 0 2157 1200 6 53 4 0 4211 300 x 200 1 15 9 0 0369 500 x 200 1 19 2 0 0653 250 2 18 3 0 0439 250 2 22 2 0 0777 300 2 19 4 0 0569 300 2 23 5 0 1007 350 2 20 5 0 0699 350 2 24 8 0 1237 400 2 21 5 0 0829 400 2 26 1 0 1467 450 3 ...

Страница 7: ...4 400 2 39 9 0 3381 450 3 36 8 0 2630 450 3 47 2 0 3668 500 3 38 4 0 3010 500 3 49 2 0 4198 600 3 41 7 0 3770 600 3 53 2 0 5258 700 4 49 8 0 4355 700 4 59 9 0 6074 800 4 53 1 0 5115 800 4 63 8 0 7134 900 5 58 5 0 5700 900 5 70 5 0 7950 1000 5 61 8 0 6460 1000 5 74 5 0 9010 1100 6 67 2 0 7045 1100 6 81 1 0 9826 1200 6 70 5 0 7805 1200 6 85 1 1 0886 900 x 200 1 25 8 0 1221 1200 x 200 1 30 8 0 1647 2...

Страница 8: ... 120 2 3 4 5 6 7 8 9 10 11 12 B 200 400 600 800 1000 1200mm B 250mm B 300 450mm B 350 500 700 900 1100mm w m s Δps Pa II TECHNICAL DATA Pressure loss Determination of pressure loss by using diagram ρ 1 2 kg m3 Δps static pressure drop w air velocity in the free cross section AxB B height of the damper ...

Страница 9: ...00 Total w m s 2 15 23 28 28 27 25 22 8 34 3 24 32 37 37 36 34 31 17 43 4 31 39 44 44 43 41 38 24 50 5 36 44 49 49 48 46 43 29 55 6 41 49 54 54 53 51 48 34 60 7 45 53 58 58 57 55 52 38 64 8 48 56 61 61 60 58 55 41 67 9 49 57 62 62 61 59 56 42 68 10 51 59 64 64 63 61 58 44 70 11 53 61 66 66 65 63 60 46 72 12 55 63 68 68 67 65 62 48 74 w air velocity in the free cross section AxB i e before blades f...

Страница 10: ...lastic foil for protection during transport and must not be used for long term storage of the equipment Changes in temperature during transport may cause condensation of water vapour inside the packaging and thereby condisitions may arise inside the packaging that are suitable for corrosion of materials used in the equipment e g white corrosion on zinc coated items or mould on calcium silicate The...

Страница 11: ...ns Before entering the dampers into operation after assembly and after sequential revisions checks and functionality tests After entering into operation these revisions must be done according to requirement set by national regulations In case that dampers are found unable to serve for their function for any cause it must be clearly marked The operator is obliged to ensure that the damper is put in...

Страница 12: ...ual product information see www mandik co uk MANDÍK a s Dobříšská 550 267 24 Hostomice Czech Republic Tel 420 311 706 742 E Mail mandik mandik cz Manufacturer MANDIK UK Ltd 130 Aztec West Bristol BS32 4UB United Kingdom Tel 44 117 4526376 E Mail help mandik co uk Authorized representative ...

Отзывы: