Fire damper - FDMQ 120
Page 34
Version 2023-03-07
TPM 162/22
Installation outside solid wall construction
■
For connection following duct
■
Minimum and maximum distance between the wall and fire damper is unlimited.
■
When installing the insulation, follow the ISOVER manufacturer's instructions.
■
The damper and the duct must be suspended separately.
■
The duct must be suspended on both sides of damper acc. to national rules.
■
Duct between fire damper and fire separating construction must be suspended by using threaded rods and mounting profiles, or another
anchoring system acc. to national standards.
■
The damper inspection openings are covered by insulation and therefore it's necessary to make inspection openings on the connecting duct.
■
Load of the suspension system depends on weight of the fire damper and duct system
■
Max. length between two suspension systems is 1500 mm.
■
Installation of the damper must be done so as all load transfer from the fire separating construction to the fire damper is absolutely excluded.
■
If the threaded rod is located inside the duct insulation, distance between threaded rod and duct is max 30 mm.
■
If the threaded rod is located outside the duct isolation, distance between threaded rod and isolation is max. 40 mm.
■
The insulation boards are fastened to the duct.
■
Reinforcing frame VRM-Q 120 must always be used for this type of installation. VRM-Q 120 is not a part of the fire damper and must be ordered
separately for each installation case!
Outside solid wall construction - ISOVER Ultimate Protect - Weichschott
EIS 120
1
FDMQ 120
2
Solid wall construction
3
Weichschott (e.g. Firestop Board HILTI CFS-CT B 1S 140/50 - min. density
140 kg/m
3
+ Firestop acrylic sealant HILTI CFS-S ACR or equivalent)
4
Fire stop coating thickness 1 mm (e.g. HILTI CFS-CT, PROMASTOP-CC or
equivalent)
5
Insulation board made of stone wool, with a surface treatment of
aluminum foil, min. density 66 kg/m³ (ISOVER Ultimate Protect SLAB 4.0
Alu1, th. 80 mm)
6
Standard air ducts, made of galvanized sheet thickness 0,8 mm, flanges
30 mm, acc. to EN 1507 and DIN 24190
7
ISOVER Protect BSK glue - apply on the insulation and stick it to the fire
separation construction
8
Fire resistant mastic - fill the gap on both sides of the fire separation
construction and around the perimeter of penetration and damper
casing. (e.g. HILTI CFS-S ACR)
9
Fixing profile with threaded rod
10
Duct penetration insulation collar - ISOVER Ultimate Protect SLAB 4.0
Alu1, th. 80 mm - glued (pos. 7) and fixed with screws to the wall
construction
11
Insulating collar of the damper and duct connection - ISOVER Ultimate
Protect SLAB 4.0 Alu1, th. 80 mm
12
L-profile 30x30x3 mm - dimensions and installation acc. to ISOVER
manufacturer
13
Stud-welded pins 80 mm - quantity and placing acc. to ISOVER manufa.
14
Stud-welded pins 160 mm - quantity and placing acc. to ISOVER manufa.
15
Stud-welded pins 240 mm - quantity and placing acc. to ISOVER manufa.
16
Fire spiral shaped screws - quantity and placing acc. to ISOVER manufa.
17
Steel clamp min. M8 bolts
18
ISOVER Protect BSF
19
VRM-Q 120
(continued on next page)
≥
100