CHANGING THE PARAMETERS OF THE TEMPERATURE REGULATOR
The programming of the regulator is made on different levels.
All important adjustments of the converter are listed in the user level and can be modified after removing
the key locking.
In order to remove the locking, please proceed as follows:
•
Standard indication (setting value below, actual value above (see photo)) must to be seen.
•
Press both together, key PGM and
for
5 seconds,
Indication =
Code 3
(all levels are locked)
•
Press PGM
•
Change the value from
3
to
2
by using the key
•
The display flashes after approx. 2 seconds and the alteration is taken over.
•
The user level is now cleared.
•
Press
EXIT
.
In order to go forward to the user level now, press key PGM, Indication =
User
•
Press the key PGM once again, indication =
SP
(setting value, adjustment at works
350
or
680
depending on converter cartridge)
•
Press key
, indication =
ALSE
(temperature range for sensor and heating control, adjust-
ment at works
10
)
•
Press
, indication =
Lo-t
(relative temperature to temperature setting value for low tempera-
ture alarm, adjustment at works -
10
)
•
Press
, indication =
rASL
(ramp gradient, temperature increase in °C/min, adjustment at
works
30
)
In order to change one of these parameters, you must press the PGM key again after
SP
,
ALSE
,
Lo-t
or
rASL
are to be read on the display. The respective value is flashing now on the display and can
be modified by using the keys
or
.
The automatic taking over of the setting value is made after approx. 2 seconds; this is indicated by a
short flash of the modified value.
If you press the keys
for a longer time, the speed of changing is increased. The value can only
be changed within the admissible range of value.
The abortion of the input is made with
EXIT
before a new value
hasn’t been taken over. After an abortion,
the standard indication is shown.
In order to switch on again the key locking, change the code to 3 again as described above.
N O T E !
If you reduce the setting value by more than 10 °C [18 °F], the sensor control
will be released and the heating circle switched off. For the reset, wait until
the value remains under the new setting value, switch off the mains voltage
and switch it on again.
Содержание CG Series
Страница 1: ...Gas Converter CG CG 2 2M CG 2H W 2MH W Instruction Manual Version 1 04 00 ...
Страница 8: ...8 CG 2 1 04 00 www mc techgroup com Hot surface Contact may cause burn Do not touch ...
Страница 33: ...www mc techgroup com CG 2 1 04 00 33 Figure 11 Wiring plan CG 2M Drawing No 2224 5 04 0 ...
Страница 34: ...34 CG 2 1 04 00 www mc techgroup com Figure 12 Wiring plan CG 2MH W Drawing No 2224 5 04 4 ...
Страница 35: ...www mc techgroup com CG 2 1 04 00 35 Figure 13 Wiring plan CG 2H W Drawing No 2224 5 04 5 ...