Accuracy*:

  ± 1% FS

Overpressure:

  10 PSID

Supply Voltage:

  12–40 VDC

                              12–35 VAC (VDC output units only)

Supply Current:

  VDC Units – 10 mA max.

                               mA Units – 20 mA max.

Enclosure:

  18 Ga C. R. Steel NEMA 4 (IP-65) 

                      6061T aluminum probe

Finish:

  Baked on enamel – PMS2GR88B

Conformance:

  EMC Standards EN50082-1(1992)

                            EN55014(1993)/EN60730-1(1992)

Compensated Temp Range:

  25°F to 150°F (-4°C to 65°C)

T. C. Error:

  ±0.0125%/°F (.02%/°C)

Operating Temp Range:

  0°F to 175°F (-18°C to 80°C)

Media Compatibility:

  Clean dry air or any inert gas

Environmental:

  10–90%RH Non-Condensing

Termination:

  Unpluggable screw terminal block

Wire Size:

  12 Ga max.

Load Impedance:

  1.6K ohms max. at 40 VDC (mA 

                                  output units)

                                 1K ohms min. (VDC output units)

Weight:

  Enclosure 1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

RANGE

OUTPUT

SPECIFICATIONS

Inspection

Requirements

Mounting

R10 ("wc)     

R11 ("wc)

R12 (pa)

R13 (pa)

0 TO 5.0 / 0 TO 2.5 / 0 TO 1.25

0 TO 15.0 / 0 TO 7.5 / 0 TO 3.75

0 TO 1250 / 0 TO 625 / 0 TO 312.5

0 TO 3750 / 0 TO 1875 / 0 TO 937.5

(4–20 mA 2-wire)

(0–5 VDC/0–10 VDC
field selectable)

mA

VDC

For Additional Information See PR-276 Data Sheet

INSTALLATION

8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA

800-843-5116 • 952-556-4900 • Fax 952-556-4997

[email protected] • www.mamacsys.com

Model PR-276

Technical Information

TI.276-03

DUCT PRESSURE TRANSDUCER

Inspect the package for damage. If damaged, notify the 
appropriate carrier immediately. If undamaged, open the 
package and inspect the device for obvious damage. 
Return damaged products.

Warning:

• 

Do not use on oxygen service, in an explosive/hazardous
environment, or with flammable/combustible media.

  Disconnect power supply before installation to prevent 

electrical shock and equipment damage.

  Make all connections in accordance with the job wiring 

diagram and in accordance with national and local 
electrical codes. Use copper conductors only.

Caution:

  Use electrostatic discharge precautions (e.g., use of wrist 

straps) during installation and wiring to prevent equipment 
damage.

  Avoid locations where severe shock or vibration, excessive 

moisture or corrosive fumes are present. NEMA Type 4 
housings are intended for outdoor use primarily to provide 
a degree of protection against wind-blown dust, rain, and 
hose-directed water.

  Do not exceed ratings of the device.

Refer to 

Figure 7 

for mounting dimensions.

1.  Remove the transducer cover using a Phillips head 

screwdriver.

2.  Select the mounting location.

3.  Mount transducer on a vertical surface with two #8 self-tapping 

screws (

not provided)

.

4.  Pull wires through bottom of enclosure and make necessary 

connections.

5.  Replace cover and make pneumatic connections.

 Tools 

(

not provided

)

-  Digital Volt-ohm Meter (DVM)
-  Appropriate screwdriver for mounting screws
-  Appropriate drill and drill bit for mounting screws

 Appropriate 

accessories

  Two #8 self-tapping mounting screws (

not provided

)

  Training: Installer must be a qualified, experienced technician

Wiring

Use maximum 12 AWG wire for wiring terminals. Refer to 

Figures 

1, 2, 3, 

4

 for wiring information and 

Figures 5

 & 

6

 for switch 

designations.

(Wiring Instructions continued on pages 2 and 3.)