7. Start-up
│
UK
65
7.4.1 Supply air volumetric flow setting
1. Connect the voltmeter (measurement
range U
DC
1...10 V) to connector pins
1 and 3 (GND).
2. Select the corresponding ventilation level
1, 2 or 3 on the room air control (operator
unit).
3. Deactivate the CO2 sensor
(jumper 10 = open).
4. You can now set the defined voltage for
the required supply air volumetric flow for
the selected ventilation level (1, 2 or 3)
with one of the blue potentiometer
adjusters S1, S2 or S3.
You will find the defined voltage value for
the required volumetric flow in the table in
Chapter 7.3 (predefined voltage = f (volu-
metric flow).
Blue adjuster S1
for the predefined
voltage of ventilation level 1
Blue adjuster S2
for the predefined
voltage of ventilation level 2
Blue adjuster S3
for the predefined
voltage of ventilation level 3
7.4.2 Exhaust air volumetric flow setting
1. Connect the voltmeter (measurement
range U
DC
1...10 V) to connector pins 5
and 3 (GND).
2. Proceed exactly as described for supply air
volumetric flow setting and adjust the
defined voltage for the required exhaust air
volumetric flow with one of the
red
poten-
tiometer adjusters S1, S2 or S3.
Red adjuster S1
for the predefined voltage
of ventilation level 1
Red adjuster S2
for the predefined voltage
of ventilation level 2
Red adjuster S3
for the predefined voltage
of ventilation level 3
8. Accessories
Accessory / Product type
Article no.
10x WSG 170 air filter,
class G4
0093.0270
Push-in frame WSG-ES 170
for G4 air filter
0093.0269
1x WSF 170 pollen filter,
class F7
0093.0271
1x WSF-AKF 170 active
carbon air filter, class F7
0093.0272
Temperature sensor with
grommet NTC 15
0157.0833
RLS 1 WR room air control
0157.0809
RLS D1 WR digital control
0157.0828
SKD CO
2
sensor
0157.0345
VOC sensor: EAQ 10/2 air
quality controller
0157.0834
Heat exchanger:
Right-hand version
Left-hand version
Enthalpy heat exchanger
(there is only one version
for left and right)
E192.0570.9000
E192.0570.9100
E192.0612.9000
Combi wall support, right-
hand version, suitable for
WS 170 R, WS 170 KR
and WS 170 KBR
KWH 12 R
KWH 16 R
0152.0058
0152.0060
Combi wall support, left-
hand version, suitable for
WS 170 L, WS 170 KL and
WS 170 KBL:
KWH 12 L
KWH 16 L
0152.0059
0152.0061
Plug connector with lip seal
SVR 125
0055.0183
B90-125
pipe elbow
0055.0312
Содержание WS 170 L
Страница 3: ......
Страница 36: ...DE 12 Anhang Verdrahtungsplan WS 170 Standardger t 34 12 1 Verdrahtungsplan WS 170 Standardger t...
Страница 38: ...DE 12 Anhang Verdrahtungsplan WS 170 Komfortger t 36 12 2 Verdrahtungsplan WS 170 Komfortger t...
Страница 40: ...DE 12 Anhang KNX Bus Konzept 38 12 3 KNX Bus Konzept...
Страница 72: ...UK 12 Appendix Wiring diagram for WS 170 standard unit 70 12 1 Wiring diagram WS 170 standard unit...
Страница 74: ...UK 12 Appendix Wiring diagram for WS 170 comfort unit 72 12 2 Wiring diagram for WS 170 comfort unit...
Страница 76: ...UK 12 Appendix KNX bus concept 74 12 3 KNX bus concept...
Страница 112: ...FR 12 Annexe Sch ma de c blage appareil standard WS 170 110 12 1 Sch ma de c blage Appareil standard WS 170...
Страница 114: ...FR 12 Annexe Sch ma de c blage appareil confort WS 170 112 12 2 Sch ma de c blage Appareil confort WS 170...
Страница 116: ...FR 12 Annexe Concept bus KNX 114 12 3 Concept bus KNX...
Страница 119: ......
Страница 120: ......
Страница 121: ......