Installations-, Inbetriebnahme- und Wartungsanleitung WS 160 Flat, WS 300 Flat
Installation, Commissioning and Maintenance Instructions for WS 160 Flat, WS 300 Flat
Notice d'installation, de mise en service et d'entretien WS 160 Flat, WS 300 Flat
EN
17
Maico Elektroapparate-Fabrik GmbH
I
Steinbeisstr. 20
I
78056 Villingen-Schwenningen
I
Germany I S49 7720 6940 I [email protected]
0185.1242.0001_RLF.9_12.22_DSW-AS
Figures:
WS 160 Flat ventilation unit
Figures:
WS 300 Flat ventilation unit
3. Slightly loosen the two screws on the electronics unit.
4. Take the electronics unit out of the ventilation unit and
attach to studs.
5. Install optional additional circuit board(s) ZP 1 and/or
ZP 2 in the slots and connect with the provided connec-
tion cables. Check DIP switch settings and adjust if ne-
cessary. For electrical connection and DIP switch set-
tings mounting instructions for respective accessories.
6. Plug optional KNX plug-in module (K-SM) or EnOcean
plug-in module (E-SM) into slot X01 of the main board
→installation instructions of the accessories.
7. Guide connecting cable of operating units and addi-
tional components through cable feedthrough(s) into
ventilation unit. Ensure seal integrity (IP protection).
8. Produce electrical connection: Wire up electrics of con-
nection cables according to wiring diagram →
.
9. For connection variants of the additional components
→ installation instructions of the accessories.
10. Install control unit(s) → and installation instructions of
the accessories.
11. Insert and screw down electronics unit.
13. Run function test: Switch the mains fuse on. The
LEDs
on the
RLS 1 WR
switch on.
14. Download commissioning software. For system require-
.
15. Set up and regulate ventilation unit.
10 Installation of the RLS 1 WR control unit
Installation conditions: Install a flush-mounted
box at the installation location of the RLS 1 WR
and guide in the connection cable.
1. Remove cover of the
RLS 1 WR
.
2. Connect the connection cable to the
RLS 1 WR
→ Wir-
ing diagrams.
3. Use 2 screws to secure the
RLS 1 WR
to the flush-
mounted box.
4. Fit cover of the
RLS 1 WR
.
11 Installation of the RLS T2 WS control unit
11.1 Retrofitting the RLS T2 WS control unit
NOTICE Incorrect wiring will result in unit damage.
Be sure to note the writing on the control unit and control
circuit board. Only connect as shown in the enclosed wir-
ing plan.
The commissioning software must be installed
for the touchscreen control unit. For download and
further information see Chapter 1, Instructions,
Software, Links, Videos.
Recommended installation position of the room temper-
ature sensor (bottom side of the RLS T2 WS)
• Installation height approx. 1.5 m
• Not in direct sunlight
• Not above sources of heat
• Not in cold draughts (doors, windows)
Preparations for installation, to be made by customer
1. Flush-mounted box at installation location.
2. Route connection cables at installation location. Per-
mitted: Shielded control cable, e.g. LIYY 4 x 0.34 mm².
Fitting control unit at installation location
3. Fit supplied mounting plate on flush-mounted box.
4. Wire supplied connector plug.
5. Attach the control unit (steps ① to ③) → Wiring dia-
grams.
6. Plug connector plug into control unit and screw in.
7. Push the control unit onto the mounting plate and snap
it into place.
8. Check the functions on the control unit.
Lead the connection lines into the ventilation unit and
wire them electrically
9. Remove front cover of ventilation unit → Ceiling/wall
installation.
10. Remove the screw on the electronics slide-in module,
pull the electronics slide-in module out of the electron-
ics compartment and hook it into the securing groove
of the ventilation unit frame.
NOTICE If the connection cables are too short, the elec-
tronics slide-in module cannot be fully pulled out/fitted.
Ensure connection cables of a sufficient length inside the
ventilation unit.
NOTICE Danger of short-circuits/damage to unit should
water enter the electronics compartment.
Ensure correct, tight line feedthrough the cable feed-
through.
11. Correctly push through cable feedthrough.
12. Guide connection cable through cable feedthrough into
ventilation unit.
13. Check for leaks and remedy any found.
Only guide connection cable individually
through the cable feedthrough. Feedthroughs
which are not needed must remain sealed.
14. Wire cables electrically on the control circuit board A2,
terminal block X11 (RS 485), according to the wiring
diagram of the ventilation unit → Wiring diagrams.
15. Push the electronics slide-in module into the electron-
ics compartment and screw it tight.
16. Attaching front cover.
17. Switch on the mains fuse, the ventilation unit switches
on.
18. Use the
Commissioning software
to set the
Basic set-
tings / Comfort control unit parameter
to
RLS T2 WS
.
19. Test settings and functions.