UK | 16 Changing the air filter
58
16 Changing the air filter
Filter change display:
Once the set filter
change interval has elapsed, a filter change
message appears on the screen
menu
Ventilation/System status.
The LED of the active ventilation level flashes
regularly on the simple control unit.
Information about previous filter changes is
stored in the menu
Reports/Filter service life
.
16.1 Filter change – filter service life
i
The manufacturer recommends the
following
.
Check the air filters (unit, external and room
filters) regularly, depending on the amount of
dirt.
Select shorter change intervals if a lot
of dust or dirt is produced. Change them as
required.
Only use original air filters.
●
G4, M5 and F7 unit filters every 3 months
●
External filters (optional) every 6 months
●
Room filters (optional) every 2 months
16.2 Filter orders
i
Orders:
Go to the
Ventilation/Filter/
Action
menu to order the right air filter
directly ex factory.
Querying filter service life:
Go to
the
Ventilation/Filter
menu to view the
current remaining filter lives.
WS 310/410/320/470
WS 170
WS 160 Flat
Filter type
Article no.
310/410
320/470
170
Flat
Unit filter G4
0092.0560 0093.0270
Pollen filter F7
0092.0559 0093.0271
External filter
–
–
Room filter
–
–
Active carbon filter
(optional)
0092.0563 0093.0272
TRIO
Filter type
Article no.
Trio
M5 exhaust air filter,
variant Q
GVT 20000020
M5 exhaust air filter,
variant L
GVT 20000022
F7 pollen filter,
variant Q and L
GVT 20000021
16.3 Changing G4, M5 and F7
unit filters
–
with filter change display –
An imminent filter change is displayed on a
main control unit – the
Status display
must
be activated under
Basic settings
. With the
simple control unit, the LED of ventilation
level II flashes regularly, at longer intervals.
i
Recommendation:
Change all unit
filters at the same time.
1. Switch off ventilation unit, disconnect at
all poles from the power supply, secure
against being accidentally switched back
on and position a visible warning sign.
2. Removing front cover(s):
310/410
320/470
Tilt front plate forwards at the two top
corners (magnets [M]) and remove from
above. Remove filter cover [A].