UK | 10 Humidity
54
10 Humidity
Set the desired humidity range to suit your
physical comfort in this menu.
The humidity value currently measured ap-
pears in the
Overview
or
Humidity
menu.
Dehumidification of the living areas with in
-
tensive ventilation generally takes place when
the
Rel. humidity max value limit
is exceeded.
With
linear sensor control
Between the
min
and
max value limit,
the air
volume (volumetric flow) needed for dehumid
-
ification changes in a continuously variable
fashion between reduced ventilation and
intensive ventilation.
Reduced ventilation (level I) activates when
the value falls below the set
Rel. humidity min
value limit
.
With
stepped sensor control
The unit increases to intensive ventilation when
the
Humidity max value limit
is exceeded.
i
In the case of unsuitable outside air
that is too humid (summer storms),
the intelligent control deactivates the
dehumidification function.
For adjusting the room humidity values
in the event of sensor measurement devia-
tions
Chapter 17.6.
Rel. humidity min value limit
Lower value limit for needs-based humidity
control in Auto Sensor operating mode
– with
linear
setting.
Ventilation unit switches to ventilation level I
(reduced ventilation) when value falls below
Humidity min value limit
.
This function is deactivated if humidity control
is set to
stepped
.
Rel. humidity max value limit
The
Humidity max value limit
is always used
as a switching point for dehumidification,
regardless of the set operating mode (excess
humidity protection).
Ventilation unit switches to ventilation level
III (intensive ventilation) when value exceeds
Humidity max value limit
.
If the value falls below the value limit with
needs-based humidity control (Auto Sensor
operating mode,
linear
setting), humidity is
controlled in a continuously variable fashion
according to automatic humidity function.
With the
stepped
setting, the value limit
serves as a switching point for switching the
humidity control on/off.