UK | 8 Ventilation
48
8.2.2 Manual operation mode
The ventilation unit runs at one ventilation
level, until another level or operating mode is
selected – with pulse ventilation, time-limited
increase to intensive ventilation.
If operating with a simple control unit or an
EnOcean wireless component, the operating
modes described in Chapter 5 apply.
i
In
manual operation
the measure-
ments of all internal and external hu-
midity sensors are taken into account.
Connected external air quality sensors
(CO
2
and VOC) are not taken into
account.
i
Excess humidity protection for the unit
is active at all times. All measurements
from internal and external humidity
sensors are used for analysis. If the
maximum humidity value limit is ex-
ceeded, a switch is made to intensive
ventilation until the humidity is 3 %
below the value limit. The ventilation
level is only increased to intensive
ventilation if the outside air conditions
are actually suited to dehumidification.
8.2.3 Auto Time operating mode:
automatic operation with time programmes
Auto Time
activates time-controlled automatic
operation with the
Winter
or
Summer
time
programme and up to 4 time intervals
and ventilation levels per day of the week.
Time programmes can be set up under
Venti-
lation time programme
Chapter 8.3.
If times within a time programme overlap,
the fans run in the higher ventilation level.
The fans switch off for times not taken into
account.
If the ventilation level is changed manually,
the automatic function is temporarily switched
off. Once a timer time has elapsed, the
ventilation unit switches back into automatic
operation.
i
In
Auto Time
operating mode, the
measurements of all internal and ex-
ternal humidity sensors are taken into
account. Connected external air quality
sensors (CO
2
and VOC) are not taken
into account.
i
Excess humidity protection for the unit
is active at all times. All measurements
from internal and external humidity
sensors are used for analysis. If the
maximum humidity value limit is ex-
ceeded, a switch is made to intensive
ventilation until the humidity is 3 %
below the value limit. The ventilation
level is only increased to intensive
ventilation if the outside air conditions
are actually suited to dehumidification.