UK | 10 Start-up
10 Start-up
Basic settings on the room air control are
undertaken in service mode. If connected to
RLS 45 K, the commissioning software may
also be used.
Switch on ventilation system as follows:
Ensure that all ventilation units and system
components are connected to the room air
controls.
Remove warning sign from fuse box and
switch on mains fuse. The ventilation units
start up in ventilation level 2.
Run function test.
Set the desired parameter values in
service
mode
or using the commissioning software.
i
Basic settings
can be undertaken
directly on the RLS 45 O or RLS 45 K
room air control.
To do this, select
service mode
and
set the desired parameter value. Addi-
tional information can be found in the
online
commissioning instructions
(download from www.maico-ventila-
toren.com).
Here you can also download the
com-
missioning software for the RLS 45
K
control. This provides a large num-
ber of setting parameters for individual
system adaptations.
10.1 Service mode – operation
Starting service mode
+
+
+
Press both
buttons for
5 seconds.
Operating mode
LED flashes. You
are in the 1st
sub-menu
(number of unit
pairs, ventilation
level etc.)
Chap. 10.2 to
10.4.
Cycle: selecting parameter
/
You can
switch be-
tween the
sub-menus
by pressing
the button
once.
Flashing ope-
rating mode LEDs
indicate
the current sub-
menu item */**
Chap. 10.2
to 10.4.
* Illuminated ventilation level LEDs indicate
the parameter currently set.
** For PP45 RC, the red flashing LED indi
-
cates the parameter currently set.